Overcurrent, Voltage, Synchronism Check, Frequency, and Power Elements
Power Elements (Available in Firmware Version 7)
Power Elements (Available in Firmware Version 7)
Four independent power elements are available. For wye-connected systems,
either single-phase power elements or three-phase power elements may be
enabled (but not both). For delta-connected systems, only three-phase power
elements may be enabled. The group setting EPWR determines how many
(and what type of) power elements are enabled:
EPWR =
N
(none), 1, 2, 3, 4 (single-phase); 3P1, 3P2, 3P3, 3P4 (three-
phase) {wye-connected voltages}
EPWR =
N
(none), 3P1, 3P2, 3P3, 3P4 (three-phase) {delta-connected
voltages}
Each enabled power element can be set to detect real power or reactive power.
With SEL
OGIC
control equations, the power elements provide a wide variety
of protection and control applications. Typical applications are:
➤
Overpower and/or underpower protection/control
➤
Reverse power protection/control
➤
VAR control for capacitor banks
Power Elements
Settings
The power element type settings are made in reference to the
load
convention:
➤
+WATTS: positive or forward real power
➤
–WATTS: negative or reverse real power
Table 3.14
Single-Phase Power Element Settings and Setting Ranges
(EPWR = 1, 2, 3, or 4)
Settings
Definition
Range
PWR1P, PWR2P,
PWR3P, PWR4P
Power element pickup
OFF, 0.33–13000.00 VA secondary,
single-phase (5 A nominal phase current
inputs,
IA
,
IB
,
IC
)
OFF, 0.07–2600.00 VA secondary,
single-phase (1 A nominal phase current
inputs,
IA
,
IB
,
IC
)
PWR1T, PWR2T,
PWR3T, PWR4T
Power element type
+WATTS, –WATTS, +VARS, –VARS
PWR1D, PWR2D,
PWR3D, PWR4D
Power element time
delay
0.00–16000 cycles, in 0.25-cycle steps
Table 3.15
Three-Phase Power Element Settings and Setting Ranges
(EPWR = 3P1, 3P2, 3P3, or 3P4)
Settings
Definition
Range
3PWR1P,
3PWR2P,
3PWR3P,
3PWR4P
Power element pickup
OFF, 1.00–39000.00 VA secondary,
three-phase (5 A nominal phase current
inputs,
IA
,
IB
,
IC
)
OFF, 0.20–7800.00 VA secondary,
three-phase (1 A nominal phase current
inputs,
IA
,
IB
,
IC
)
PWR1T, PWR2T,
PWR3T, PWR4T
Power element type
+WATTS, –WATTS, +VARS, –VARS
PWR1D, PWR2D,
PWR3D, PWR4D
Power element time
delay
0.00–16000 cycles, in 0.25-cycle steps
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...