![Schweitzer Engineering Laboratories SEL-321 Instruction Manual Download Page 132](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-321/sel-321_instruction-manual_1216711132.webp)
3-22
Communications
Date Code 20011026
SEL-321/321-1 Instruction Manual
SHOWSET
SHOWSET displays the relay settings of the currently selected group. Type SHOWSET with a
group number (1 - 6) to view the group settings for that particular group. Append this command
with an "A" to cause all settings, including inactive settings, to be displayed; normally, settings
for disabled functions are not shown. Enter parameters following SHOWSET command in any
order.
Settings cannot be entered or modified with this command. Change settings with the SET
command family under Level 2 Access. The SHOWSET command results in the following
display:
=>SHOWSET 2 <ENTER>
SHOWSET 2 <ENTER>
SHOWSET 2 <ENTER>
SHOWSET 2 <ENTER>
GROUP 2
RELID =SEL-321 POTT
TRMID =EXAMPLE: BUS B, BREAKER 3
Z1MAG = 7.80 Z1ANG = 83.97 Z0MAG = 24.79 Z0ANG = 81.46
LOCAT = Y LL = 100.00 CTR = 200.0 PTR = 2000.0
PMHOZ = 3 GMHOZ = 3 QUADZ = 3
DIR1 = F DIR2 = F DIR3 = R DIR4 = F
Z1P = 6.24 Z2P = 9.36 Z3P = 1.87
50PP1 = 2.55 50PP2 = 2.22 50PP3 = 2.45
Z1MG = 6.24 Z2MG = 9.36 Z3MG = 1.87
XG1 = 6.24 XG2 = 9.36 XG3 = 1.87
RG1 = 2.50 RG2 = 5.00 RG3 = 6.00
50L1 = 0.90 50L2 = 0.90 50L3 = 1.30
50G1 = 0.90 50G2 = 0.60 50G3 = 0.50
k01M = 0.726 k01A =-3.69 k0M = 0.726 k0A =-3.69 T = 0.00
EOOS = N
ELE = Y ZLF = 9.22 ZLR = 9.22
PLAF = 30 NLAF =-30 PLAR = 150 NLAR = 210
Z2F = 0.77 50QF = 0.5 Z2R = 5.45 50QR = 0.5 a2 = 0.07
E51P = N
E51N = Y 51NP = 0.74 51NC = U3
Press RETURN to continue
51NTD = 2.00 51NRS = Y 51NTC = 32QF
E50N = N
E51Q = Y 51QP = 2.20 51QC = U3
51QTD = 2.00 51QRS = N 51QTC = 32QF
E50Q = N
EVOLT = N
Z2PD = 20.00 Z3PD = 0.00
Z2GD = 20.00 Z3GD = 0.00
EPOTT = Y Z3RBD = 5.00 EBLKD = 10.00
ETDPU = 2.00 EDURD = 4.00
EDCUB = N
EZ1EXT= N
EREJO = N
ESOTF = Y ENCLO = Y CLOEND= 10.00 EN52A = N
SOTFD = 30.00 50H = 11.25
ELOP = Y LOPD = 3.00 50M = 2.37 59QL = 14.00 59PL = 14.00
EPOLD = N ESPT = N ESPO = N
3POD = 1.50 ESTUB = Y 50MFD = 20.00 TULO = 3
TDURD = 9.00 TOPD = 0.00 TXPU = 0.00 TXDO = 0.00
TYPU = 0.00 TYDO = 0.00 TZPU = 0.00 TZDO = 0.00 ITTD = 5.00
Press RETURN to continue
=>>
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......