SET (Groups)
Comment
PMHOZ must be > 1 to torque-control 51P
with M2P.
M2P is disabled if PMHOZ < 2.
PMHOZ must be > 1 to torque-control 51Q
with M2P.
M2P is disabled if PMHOZ < 2.
GMHOZ or QUADZ must be > 1 to torque-
control 51N with Z2G.
Z2G is disabled if GMHOZ and QUADZ < 2.
GMHOZ or QUADZ must be > 1 to torque-
control 51Q with Z2G.
Z2G is disabled if GMHOZ and QUADZ < 2.
ELE must be Y to torque-control 51P with
ZLIN or ZLOUT. (Applies to SEL-321-1
Relay only)
ZLIN and ZLOUT are disabled if ELE = N.
(Applies to SEL-321-1 Relay only)
Table 3.8: SET or SET G Warning Messages
Message Comment
EZ1EXT disabled until CLOSE assigned to
an input contact.
Logic scheme disabled until CLOSE is
assigned to an input.
BT must be assigned to an input contact since
DCB is enabled.
DCB scheme disabled if BT is not assigned to
an input.
EXTUL must be assigned to an input contact
to use TULO = 4.
TULO is set to 4, but EXTUL is not assigned.
Logic scheme disabled.
LOG must be assigned to an input contact
since DCUB is enabled.
DCUB scheme disabled because LOG is not
assigned to an input.
PT must be assigned to an input contact since
POTT is enabled.
POTT scheme disabled because PT is not
assigned to an input.
Assign PTXFR to an input contact to enable
trip suspicion logic.
Trip suspicion logic disabled because PTXFR
is not assigned to an input.
PROTOCOL = MB port setting required to
use RMBn.
The inputs RMB1 - RMB8 are not updated
unless Port 1 or 2 PROTOCOL = MB.
If setting changes were made to the active group, the relay enables them and pulses the ALARM
contact.
The Settings Sheet in
Section 5: Applications
gives a complete list of settings made using the
SET command. For an explanation of the use of the front-panel controls with the SET command,
see
LCD Functions and Front-Panel Commands
in this section.
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......