3-8
Communications
Date Code 20011026
SEL-321/321-1 Instruction Manual
To close the circuit breaker with this command, type
CLOSE <ENTER>
. The prompting
message "Close BREAKER (Y/N) ?" is displayed. Then "Are you sure (Y/N)?" Typing
N
<ENTER>
after either of the above prompts aborts the closing operation with the message
"Command Aborted."
If the Breaker Jumper (P7: J106) is not in place, the relay responds: "Aborted: Breaker Jumper
Not in Place."
==>CLOSE <ENTER>
CLOSE <ENTER>
CLOSE <ENTER>
CLOSE <ENTER>
Close BREAKER (Y/N) ? Y <ENTER>
Y <ENTER>
Y <ENTER>
Y <ENTER>
Are you sure (Y/N) ? Y <ENTER>
Y <ENTER>
Y <ENTER>
Y <ENTER>
Breaker CLOSED
==>
COMM
The COMM command displays integral relay-to-relay communications data. To get a summary
report, enter the command without any parameters.
=>COMM <ENTER>
COMM <ENTER>
COMM <ENTER>
COMM <ENTER>
EXAMPLE: BUS B, BREAKER 3 Date: 04/11/00 Time: 10:45:08.993
SEL-321 POTT
FID=SEL-321-1-R424-V656124pb-Z001001-D20000410
Summary for Mirrored Bits Channel
For 04/05/00 17:18:12.993 to 04/11/98 10:45:08.993
Total failures 3 Last error Re-sync
Relay disabled 1
Data error 0 Longest failure 0 00:00:00.499
Re-sync 0
Underrun 1 Unavailability 0.000688 %
Overrun 0
Parity error 1
Framing error 0
=>
Summary of Contents for SEL-321
Page 4: ......
Page 10: ......
Page 12: ......
Page 162: ......
Page 171: ...Date Code 20011026 Event Reporting 4 9 SEL 321 321 1 Instruction Manual ...
Page 263: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 264: ......
Page 265: ...SEL DIRECTION AND POLARITY CHECK FORM ...
Page 266: ......
Page 270: ......
Page 358: ......
Page 360: ......
Page 362: ......
Page 366: ......
Page 370: ......
Page 390: ......