Date Code 20010625
Setting Negative-Sequence Overcurrent Elements
F-1
SEL-311L Instruction Manual
APPENDIX F: SETTING NEGATIVE-SEQUENCE
OVERCURRENT ELEMENTS
S
ETTING
N
EGATIVE
-S
EQUENCE
D
EFINITE
-T
IME
O
VERCURRENT
E
LEMENTS
Negative-sequence instantaneous overcurrent elements 50Q1 through 50Q4 and 67Q1
through 67Q4 should not be set to trip directly
. This is because negative-sequence current
can transiently appear when a circuit breaker is closed and balanced load current suddenly
appears.
To avoid tripping for this transient condition, use negative-sequence definite-time overcurrent
elements 67Q1T through 67Q4T with at least 1.5 cycles of time delay (transient condition lasts
less than 1.5 cycles). For example, make time delay setting:
67Q1D = 1.50
for negative-sequence definite-time overcurrent element 67Q1T. Refer to Figure 3.46 for more
information on negative-sequence instantaneous and definite-time overcurrent elements.
Continue reading in
Coordinating Negative-Sequence Overcurrent Elements
in this appendix
for guidelines on coordinating negative-sequence definite-time overcurrent elements and a
following coordination example. The coordination example uses time-overcurrent elements, but
the same principles can be applied to definite-time overcurrent elements.
S
ETTING
N
EGATIVE
-S
EQUENCE
T
IME
-O
VERCURRENT
E
LEMENTS
Negative-sequence time-overcurrent element 51QT should not be set to trip directly when it
is set with a low time-dial setting
51QTD,
that results in curve times below 3 cycles
(see
curves in Figures 9.1 through 9.10 in
Section 9: Setting the Relay
). This is because negative-
sequence current can transiently appear when a circuit breaker is closed and balanced load
current suddenly appears. Refer to Figure 3.49 for more information on negative-sequence time-
overcurrent element 51QT.
To avoid having negative-sequence time-overcurrent element 51QT with such low time dial
settings trip for this transient negative-sequence current condition, make settings similar to the
following:
SV6PU = 1.50 cycles
(minimum response time; transient condition lasts
less than 1.5 cycles)
SV6 = 51Q
(run pickup of negative-sequence time-overcurrent
element 51QT through SEL
OGIC
control equation
variable timer SV6)
TR = … + 51QT * SV6T + …
(trip conditions; SV6T is the output of the SEL
OGIC
control equation variable timer SV6)
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......