Date Code 20011112
Firmware Upgrade Instructions
B-1
SEL-311L Instruction Manual
APPENDIX B: FIRMWARE UPGRADE INSTRUCTIONS
F
IRMWARE
(F
LASH
) U
PGRADE
I
NSTRUCTIONS
SEL may occasionally offer firmware upgrades to improve the performance of your relay. The
SEL-311L Relay stores firmware in Flash memory; therefore, changing physical components is
not necessary. A firmware loader program called SEL
BOOT
resides in the SEL-311L Relay.
These instructions give a step-by-step procedure to upgrade the relay firmware by downloading a
file from a personal computer to the relay via a serial port.
I
MPORTANT
N
OTE
R
EGARDING
S
ETTINGS
The firmware upgrade procedure may result in lost relay settings due to the addition of new
features and changes in the way memory is used. It is imperative to have a copy of the original
relay settings available in case they need to be re-entered. Carefully following these upgrade
instructions will minimize the chance of inadvertently losing relay settings.
The communications processor (SEL-2020 or SEL-2030) will need to be re-autoconfigured for
the port connected to a relay that has been firmware upgraded. Failure to do so may cause
automatic data collection failure if the communication processor’s power is cycled.
R
EQUIRED
E
QUIPMENT
•
Personal computer.
•
Terminal emulation software that supports XMODEM/CRC protocol (e.g., CROSSTALK
®
,
Microsoft
®
Windows
®
Terminal and HyperTerminal, Procomm
®
Plus, Relay/Gold, or
SmartCOM).
•
Serial communications cable (SEL
-
234A or equivalent).
•
Disk containing firmware upgrade file.
U
PGRADE
P
ROCEDURE
The instructions below assume you have a working knowledge of your personal computer
terminal emulation software. In particular, you must be able to modify your serial
communications parameters (baud rate, data bits, parity, etc.), disable any hardware or software
flow control in your computer terminal emulation software, select transfer protocol (i.e.,
XMODEM/CRC), and transfer files (e.g., send and receive binary files).
1. If the relay is in service, disable its control functions.
Note:
If the SEL-311L Relay contains History (HIS) data, Event (EVE) data, Metering
(MET) data, or Sequential Events Recorder (SER) data that you want to retain,
you must retrieve this data prior to performing the firmware upgrade, because all
of these data sets may be erased in the upgrade procedure.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......