Date Code 20010625
Standard Event Reports and SER
12-9
SEL-311L Instruction Manual
Figure 12.3: External Fault
Filtered and Unfiltered Event Reports
The SEL-311L Relay samples the basic power system measurands (ac voltage, ac current, station
battery, and optoisolated inputs) 16 times per power system cycle. The relay filters the
measurands to remove transient signals. The relay operates on the filtered values and reports
them in the event report.
To view the raw inputs to the relay, select the unfiltered event report (e.g.,
EVE R
or
EVE B R
).
Use the unfiltered event reports to observe:
v
Power system harmonics on the voltage and current channels
v
Decaying dc offset during fault conditions on current channels
v
Optoisolated input contact bounce
v
Transients on the station dc battery channel Vdc (power input terminals Z25 and Z26)