10-12
Line Current Differential Communications
Date Code 20010625
and Serial Port Communications and Commands
SEL-311L Instruction Manual
=>>COMM Y L <ENTER>
SEL-311L Date: 05/26/01 Time: 09:27:03.269
EXAMPLE: BUS B, BREAKER 3
FID=SEL-311L-R100-V0-Z001001-D20010625 CID=BAFD
Summary for 87L Channel Y
Channel Status Alarms
ROKY = 1 DBADY = 0 RBADY = 0 AVAY = 0
For 05/24/01 13:37:01.631 to 05/26/01 09:27:04.248
COMMUNICATION LOG SUMMARY COMMUNICATION STATISTICS
# of Error records 29 Last error Data Error
Data Error 20 Longest failure 4.685 sec.
Dropout 9 Lost Packets, prev. 24 hours 407
Test Mode Entered 0 One Way Delay (Ping-Pong) 0 msec.
Error Recovery
# Date Time Date Time Duration Cause
1 05/26/01 09:23:54.041 05/26/01 09:23:54.042 0.001 Data Error
2 05/26/01 09:23:53.888 05/26/01 09:23:54.040 0.152 Dropout Error
3 05/26/01 09:23:53.885 05/26/01 09:23:53.888 0.003 Data Error
4 05/26/01 09:23:53.882 05/26/01 09:23:53.885 0.003 Dropout Error
5 05/26/01 09:23:53.870 05/26/01 09:23:53.882 0.011 Data Error
6 05/26/01 09:23:53.851 05/26/01 09:23:53.870 0.020 Dropout Error
7 05/26/01 09:23:53.847 05/26/01 09:23:53.851 0.003 Data Error
8 05/26/01 09:23:53.846 05/26/01 09:23:53.847 0.001 Dropout Error
9 05/26/01 09:23:53.843 05/26/01 09:23:53.846 0.003 Data Error
.
.
.
25 05/26/01 09:23:51.554 05/26/01 09:23:51.654 0.100 Dropout Error
26 05/26/01 09:23:51.550 05/26/01 09:23:51.554 0.003 Data Error
27 05/24/01 13:37:04.688 05/24/01 13:37:04.689 0.001 Data Error
28 05/24/01 13:37:00.003 05/24/01 13:37:04.688 4.685 Dropout Error
29 05/24/01 13:37:00.000 05/24/01 13:37:00.003 0.003 Data Error
=>>
S
ERIAL
P
ORT
C
OMMUNICATIONS AND
C
OMMANDS
In addition to the differential communication channel(s) all SEL-311L Relay models have three
EIA-232 ports (one front and two rear) and one rear EIA-485 port. The ports are useful for relay
settings changes, interrogation, control, and data collection.
Connect the serial port to a computer serial port for local communications or to a modem for
remote communications. Other devices useful for communications include the SEL-2020 and
SEL-2030 Communications Processors, SEL-2505 Remote I/O Module, SEL-2100 Protection
Logic Processor, and SEL-DTA2 Display Transducer Adapter. You can use a variety of terminal
emulation programs on your personal computer to communicate with the relay. Examples of
PC-based terminal emulation programs include CROSSTALK
®
, Microsoft
®
Windows
®
Terminal
and HyperTerminal, Procomm
®
Plus, Relay/Gold, and SmartCOM. For the best display, use
VT-100 terminal emulation or the closest variation.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......