8-30
Breaker Monitor and Metering Functions
Date Code 20010625
SEL-311L Instruction Manual
View or Reset Demand Metering Information
Via Serial Port
See
MET Command (Metering Data)
, MET D—Demand Metering in
Section 10: Line Current
Differential Communications and Serial Port Communications and Commands
. The
MET D
command displays demand and peak demand metering for the following values:
Currents I
A,B,C
I
G
3I
2
Input currents (A primary)
Residual ground current (A primary; I
G
=3I
0
= I
A
+ I
B
+ I
C
)
Negative-sequence current (A primary)
Power MW
A,B,C
MVAR
A,B,C
MW
3P
MVAR
3P
Single-phase megawatts
Single-phase megavars
Three-phase megawatts
Three-phase megavars
The
MET RD
command resets the demand metering values. The
MET RP
command resets the
peak demand metering values.
Via Front Panel
The information and reset functions available via the previously discussed serial port commands
MET D
,
MET RD
, and
MET RP
are also available via the front-panel METER pushbutton.
See Figure 11.2 in
Section 11: Front-Panel Interface
.
Demand Metering Updating and Storage
The SEL-311L Relay updates demand values approximately every 2 seconds.
The relay stores peak demand values to nonvolatile storage once per day (it overwrites the
previous stored value if it is exceeded). Should the relay lose control power, it will restore the
peak demand values saved by the relay at 23:50 hours on the previous day.
Peak recording is momentarily suspended when SEL
OGIC
control equation setting FAULT is
asserted (= logical 1). See the explanation for the FAULT setting in the following
Maximum/Minimum Metering
Updating and Storage
subsection. It is not necessary to suspend
demand metering during a fault since fault quantities will not significantly change demand
quantities that are calculated using a minimum time constant of 5 minutes.
L
OCAL
E
NERGY
M
ETERING
View or Reset Energy Metering Information
Via Serial Port
See
MET Command (Metering Data)
, MET E—Energy Metering in
Section 10: Line Current
Differential Communications and Serial Port Communications and Commands
. The
MET E
command displays accumulated single- and three-phase megawatt and megavar hours. The
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......