Date Code 20010625
Inputs, Outputs, Timers, and Other Control Logic
7-33
SEL-311L Instruction Manual
O
UTPUT
C
ONTACTS
Operation of Output Contacts
The SEL-311L Relay contains two types of output contacts. The backup protection hardware
controls contacts OUT101 through OUT107 independent of the line current differential
hardware. Use outputs OUT101 through OUT107 for backup protection tripping, closing, and
for control applications.
The line current differential hardware controls special high-speed contacts OUT201 through
OUT206. Contacts OUT201 through OUT206 operate if both the backup protection hardware
and the dedicated line current differential hardware are healthy. Use contacts OUT201 through
OUT206 for high-speed line current differential protection, and for faster backup protection
tripping.
The distinction between the two types of contacts is an important application consideration. The
following discussion describes each type of contact, as well as how each should be used for
several example applications.
Output Contacts OUT101 Through OUT107
SEL
OGIC
control equations OUT101 through OUT107 control contacts OUT101 through
OUT107. When the SEL
OGIC
control equation evaluates to logical 1 for one of these contacts,
the relay closes normally open contacts (a), and opens normally closed contacts (b) as shown in
Figure 7.26. The PULSE command also controls contact outputs. For example, if SEL
OGIC
control equation OUT101 is set to
OUT101 = TRIP
when Relay Word bit TRIP asserts, the control coil for OUT101 is energized, and OUT101
closes if it is a normally open contact. Likewise, the command
PULSE OUT101
momentarily
energizes the control coil of contact output OUT101, and the contact closes (again assuming
OUT101 is a normally open contact). See
Output Contact Jumpers
in
Section 2: Installation
,
for output contact type options.
Notice in Figure 7.26 that contact output OUT107 also functions as an extra alarm contact when
jumper JMP23 is in position 1–2. See
ALARM Output Contact and 87HWAL
later in this
section for more information about how OUT107 operates when it is configured as an extra
alarm, and for information about how OUT107 operates as configured in a standard relay
shipment from the factory.
Contacts OUT101 through OUT107 are suitable for line current differential and backup
protection tripping, closing, and general control functions. All seven contacts are rated for
tripping duty, and typically close less than five milliseconds after the corresponding SEL
OGIC
control equation evaluates to logical 1.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......