7-30
Inputs, Outputs, Timers, and Other Control Logic
Date Code 20010625
SEL-311L Instruction Manual
Figure 7.24: SEL
OGIC
Control Equation Variables/Timers SV7/SV7T Through
SV16/SV16T
Settings Example
In the SEL
OGIC
control equation settings, a SEL
OGIC
control equation timer may be used for a
simple breaker failure scheme:
SV1
=
TRIP
The TRIP Relay Word bit is run through a timer for breaker failure timing. Timer pickup setting
SV1PU is set to the breaker failure time (SV1PU = 12 cycles). Timer dropout setting SV1DO is
set for a 2-cycle dropout (SV1DO = 2 cycles). The output of the timer (Relay Word bit SV1T)
operates output contact OUT103.
OUT103
=
SV1T