Date Code 20010625
Inputs, Outputs, Timers, and Other Control Logic
7-21
SEL-311L Instruction Manual
Operation of SEL
OGIC
Control Equation Settings SS1 Through SS6
Each setting group has its own set of SEL
OGIC
control equation settings SS1 through SS6.
Table 7.4: Definitions for Active Setting Group Switching
SEL
OGIC
Control Equation Settings SS1 Through SS6
Setting Definition
SS1
go to (or remain in) setting Group 1
SS2
go to (or remain in) setting Group 2
SS3
go to (or remain in) setting Group 3
SS4
go to (or remain in) setting Group 4
SS5
go to (or remain in) setting Group 5
SS6
go to (or remain in) setting Group 6
The operation of these settings is explained with the following example:
Assume the active setting group starts out as setting Group 3. Corresponding Relay Word
bit SG3 is asserted to logical 1 as an indication that setting Group 3 is the active setting
group (see Table 7.3).
With setting Group 3 as the active setting group, setting SS3 has priority. If setting SS3 is
asserted to logical 1, setting Group 3 remains the active setting group, regardless of the
activity of settings SS1, SS2, SS4, SS5, and SS6. With settings SS1 through SS6 all
deasserted to logical 0, setting Group 3 still remains the active setting group.
With setting Group 3 as the active setting group, if setting SS3 is deasserted to logical 0 and
one of the other settings (e.g., setting SS5) asserts to logical 1, the relay switches from
setting Group 3 as the active setting group to another setting group (e.g., setting Group 5) as
the active setting group, after qualifying time setting TGR:
TGR Group Change Delay Setting
(settable from 0.00 to 16000.00 cycles)
In this example, TGR qualifies the assertion of setting SS5 before it can change the active
setting group.
Operation of Serial Port GROUP Command and Front-Panel GROUP Pushbutton
SEL
OGIC
control equation settings SS1 through SS6 have priority over the serial port
GROUP
command and the front-panel GROUP pushbutton in selecting the active setting group. If any
one of SS1 through SS6 asserts to logical 1, neither the serial port
GROUP
command nor the
front-panel GROUP pushbutton can be used to switch the active setting group. But if SS1
through SS6 all deassert to logical 0, the serial port
GROUP
command or the front-panel
GROUP pushbutton can be used to switch the active setting group.
See
Section 10: Line Current Differential Communications and Serial Port Communications
and Commands
for more information on the serial port
GROUP
command. See
Section 11:
Front-Panel Interface
for more information on the front-panel GROUP pushbutton.
Summary of Contents for SEL-311L
Page 6: ......
Page 8: ......
Page 26: ......
Page 54: ......
Page 144: ......
Page 216: ......
Page 252: ......
Page 302: ......
Page 338: ......
Page 480: ......
Page 484: ......
Page 486: ......
Page 502: ......
Page 532: ...12 28 Standard Event Reports and SER Date Code 20010625 SEL 311L Instruction Manual 4 ...
Page 552: ......
Page 554: ......
Page 574: ......
Page 576: ......
Page 596: ......
Page 602: ......
Page 628: ......
Page 656: ......
Page 662: ......
Page 664: ......
Page 688: ......
Page 700: ......
Page 716: ......
Page 722: ......
Page 734: ......