Date Code 20060320
Loss-of-Potential, CCVT Transient Detection, Load-Encroachment, and Directional Element Logic
Directional Control for Ground Distance and Residual Ground Overcurrent Elements
Directional
Element Enables
,
, and
The directional element enables, Relay Word bits 32QGE, 32VE, and 32IE
have the following correspondence to the directional elements:
➤
32QGE (Negative-sequence voltage-polarized directional
element)
➤
32VE (Zero-sequence voltage-polarized directional element)
➤
32IE (Channel IP current-polarized directional element)
Note that
has extra directional element enable 32QE, which is used
in the logic that controls phase distance elements (see
The settings involved with 32QGE, 32VE, and 32IE in
and
(e.g., settings a2, k2, a0) are explained in
Best Choice Ground
Directional Logic
and
Relay Word bits 32QGE, 32VE, and 32IE and setting ORDER are used in the
Best Choice Ground Directional logic in
. The Best Choice Ground
Directional logic determines the order in which the directional element should
be enabled to operate. The ground distance and residual ground overcurrent
elements set for directional control are then controlled by this directional
element.
Directional Elements
,
,
, and
The enable output of Best Choice Ground Directional logic in
determines which directional element will run.
Additionally, note that if enable setting ELOP = Y or Y1 and a loss-of-
potential condition occurs (Relay Word bit ILOP asserts), the negative-
sequence voltage-polarized and zero-sequence voltage-polarized directional
elements are disabled (see
).
The channel IP current-polarized directional element does not use voltage in
making direction decisions, thus a loss-of-potential condition does not disable
the element, but rather aids in enabling it. When the internal enable 32IE is
asserted, the channel IP current-polarized directional element (
) is
enabled if enable setting ELOP = Y or Y1 and a loss-of-potential condition
occurs (Relay Word bit ILOP asserts).
and accompanying text for more information on loss-of-
potential.
Directional
Element Routing
and
.
The directional element outputs are routed to the forward (Relay Word bit
32GF) and reverse (Relay Word bit 32GR) logic points.
Loss-of-Potential
that if
all
the following are true:
Summary of Contents for SEL-311C
Page 1: ...20060320 SEL 311C Relay Protection and Automation System Instruction Manual PM311C 01 NB ...
Page 22: ...This page intentionally left blank ...
Page 42: ...This page intentionally left blank ...
Page 68: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 294: ...This page intentionally left blank ...
Page 330: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 406: ...This page intentionally left blank ...
Page 454: ...This page intentionally left blank ...
Page 574: ...This page intentionally left blank ...
Page 592: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 648: ...This page intentionally left blank ...
Page 652: ...This page intentionally left blank ...
Page 678: ...This page intentionally left blank ...
Page 682: ...This page intentionally left blank ...
Page 722: ...This page intentionally left blank ...
Page 724: ...This page intentionally left blank ...