2-14
Installation
Date Code 20011205
SEL-311B Instruction Manual
Table 2.3: Move Jumper JMP23 to Select Extra Alarm
Position
Output Contact OUT107 Operation
Output contact OUT107 is operated by Relay Word bit OUT107.
Jumper JMP23 comes in this position in a standard relay shipment (see
Figure 7.26).
“Extra Alarm” output contact is operated by alarm logic/circuitry.
Relay Word bit OUT107 does not have any effect on output contact
OUT107 when jumper JMP23 is in this position (see Figure 7.26).
If an output contact is operating as an “extra alarm” (driven by the same signal that operates the
dedicated ALARM output contact), it will be in the opposite state of the dedicated ALARM
output contact in a standard relay shipment. In a standard relay shipment, the dedicated ALARM
output contact comes as a “b” type output contact and all the other output contacts (including the
“extra alarm”) come as “a” type output contacts.
The output contact type for any output contact can be changed (see preceding subsection
Output
Contact Jumpers
). Thus, the dedicated ALARM output contact and the “extra alarm” output
contact can be configured as the same output contact type if desired (e.g., both can be configured
as “b” type output contacts).
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......