Date Code 20011205
Close and Reclose Logic
6-5
SEL-311B Instruction Manual
R
ECLOSE
S
UPERVISION
L
OGIC
Note that one of the inputs into the close logic in Figure 6.1 is:
Reclosing Relay Open Interval Time-Out (qualified by 79CLS)
This input into the close logic in Figure 6.1 is the indication that a reclosing relay open interval
has timed out, a qualifying condition (SEL
OGIC
control equation setting 79CLS) has been met,
and thus automatic reclosing of the circuit breaker should proceed by asserting the CLOSE Relay
Word bit to logical 1. This input into the close logic in Figure 6.1 is an output of the reclose
supervision logic in the following Figure 6.2.