6-4
Close and Reclose Logic
Date Code 20011205
SEL-311B Instruction Manual
SEL
OGIC
control equation setting 52A is set with optoisolated input IN101. Input IN101 is
connected to a 52a circuit breaker auxiliary contact. When a closed circuit breaker condition is
detected, the CLOSE Relay Word bit is deasserted to logical 0. Setting 52A can handle a 52a or
52b circuit breaker auxiliary contact connected to an optoisolated input (see
Optoisolated Inputs
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more 52A setting
examples).
With setting CFD = 60.00 cycles, once the CLOSE Relay Word bit asserts, it remains asserted at
logical 1 no longer than a maximum of 60 cycles. If the Close Failure Timer times out, Relay
Word bit CF asserts to logical 1, forcing the CLOSE Relay Word bit to logical 0.
Defeat the Close Logic
If SEL
OGIC
control equation circuit breaker auxiliary setting 52A is set with numeral 0
(52A = 0), then the close logic is inoperable. Also, the reclosing relay is defeated (see
Reclosing
Relay
later in this section).
Circuit Breaker Status
Refer to the bottom of Figure 6.1. Note that SEL
OGIC
control equation setting 52A (circuit
breaker status) is available as Relay Word bit 52A. This makes it convenient to set other
SEL
OGIC
control equations. For example, if the following setting is made:
52A = IN101
(52a auxiliary contact wired to input IN101)
or
52A = !IN101 (52b auxiliary contact wired to input IN101)
then if breaker status is used in other SEL
OGIC
control equations, it can be entered as 52A—the
user doesn’t have to enter IN101 (for a 52a) or !IN101 (for a 52b). For example, refer to
Rotating Default Display
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
. If
circuit breaker status indication is controlled by display point setting DP2:
DP2 =
IN101
This can be entered instead as:
DP2 =
52A
(presuming SEL
OGIC
control equation setting 52A = IN101 is made).
Program an Output Contact for Closing
In the factory settings, the resultant of the close logic in Figure 6.1 is routed to output contact
OUT103 with the following SEL
OGIC
control equation:
OUT103 = CLOSE
See
Output Contacts
in
Section 7: Inputs, Outputs, Timers, and Other Control Logic
for more
information on programming output contacts.
Summary of Contents for SEL-311B
Page 6: ......
Page 8: ......
Page 10: ......
Page 24: ......
Page 26: ......
Page 122: ......
Page 124: ......
Page 138: ......
Page 168: ......
Page 172: ......
Page 254: ......
Page 282: ......
Page 306: ......
Page 348: ......
Page 364: ......
Page 366: ......
Page 448: ......
Page 460: ......
Page 466: ......
Page 476: ......
Page 482: ......
Page 494: ......
Page 500: ......
Page 522: ......
Page 526: ......
Page 528: ......
Page 534: ......
Page 536: ......
Page 550: ......
Page 570: ......
Page 586: ......
Page 600: ......