RELAY ELEMENTS STATUS INDICATORS
The columns headed
"
Relays
"
indicate the states of all relay elements. Active states of the
various relay elements are indicated by designator symbols corresponding with the relay
element names. Inactive states are indicated by periods placed in the columns. The entries
for active relay elements are shown below.
51P: Phase time-overcurrent element
50N: Residual-overcurrent elements
50P: Phase overcurrent elements
: 1=50P1
2=50P2
3=50P3
high set picked up
medium set
low set
67P: Directional phase overcurrent elements : 1=67P1
high set picked up
2=67P2
medium set
3=67P3
low set
: P=51PP
: T=51PT
: 1=50N1
2=50N2
3=50N3
element picked up
trip threshold reached
high set picked up
medium set
low set
67N: Directional ground-overcurrent units
: 1=67N1
2=67N2
3=67N3
high set picked up
medium set
low set
51N: Residual time-overcurrent element
: P=51NP
: T=51NT
element picked up
trip threshold reached
The states of all output and input contacts are shown in the next two column groups, headed
"
Outputs
"
and
"
Inputs". Assertion of any output or input contact is indicated by an asterisk
(*) in the corresponding column; nonassertion is indicated by a period. The contents of the
columns are:
OUTPUTS
TP
:
TRIP output
CL :
CLOSE output
A l :
PROGRAMMABLE output #1
A2 :
PROGRAMMABLE output #2
A3 :
PROGRAMMABLE output #3
A4 :
PROGRAMMABLE output #4
AL :
ALARM output
Date Code 920326
Event Reporting
SEL-267D/167D Instruction Manual
4-5
Summary of Contents for SEL-167D
Page 3: ......
Page 6: ......
Page 8: ......
Page 9: ......
Page 10: ......
Page 11: ......
Page 51: ...LOGIC DIAGRAMS Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 31 ...
Page 52: ...Date Code 920326 Specifications 2 32 SEL 267D 167D Instruction Manual ...
Page 53: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 33 ...
Page 54: ...Date Code 920326 Specifications SEL 267D 167D Instruction Manual 2 34 ...
Page 88: ...SAMPLE EVENT REPORT ...
Page 114: ......
Page 115: ......