o
- Operating Instructions
Contents:
Safety Instructions
Standard Conformity
Technical Data
Dimensions
Mounting
Installation and Commissioning
Maintenance
The security of people and equipment in hazardous areas depends on the observance of all safety
standards. A condition for every maintenance work is the full knowledge of all valid regulations and
standards.
L-00815-4-07
8
Explosion-proof light fittings of series
e 152 ...
Zone 1 - equipment-category II 2 G
Zone 21 - equipment-category II 2 D
for operating bi-pin fluorescent tubes
by means of an electronic control gear
the gasket located in the housing.
- the correct installation and tightness of explosion-proof cable glands and explosion-proof locking screws.
Cleaning the light fitting:
Attention:
At the plastic parts of the luminaire there is danger of ignition due to electrostatic charging!
Therefore do not wipe the light fitting with any dry cloth!
For cleaning the housing and cover use only cold or lukewarm water together with a viscose sponge or a
soft fibrous-free cloth.
Repairing and reconditioning the luminaire:
Attention:
Replace damaged explosion-proof parts by original spare parts from the Adolf Schuch GmbH
only!
The lamp replacement has to be made according to item 6.3 of these operating instructions.
Lighting fitting in version with disconnecting switch: Before replacing the fluorecent tubes make sure that
the visible indication of the switch is ”green”.
Opening the light fitting in version without a disconnecting switch is allowed when it is idle only!
Attention:
Removing the reflector is allowed when the lighting fitting is idle only!
Adolf Schuch GmbH
Lichttechnische Spezialfabrik
Mainzer Str. 172, D-67547 Worms am Rhein
Postfach (P.B.) 2145, D-67511 Worms, Telefon: 06241/4091-0
Phone: +49 6241/4091- 0 Internet: www.schuch.de
Telefax: +49 6241/4091- 29 E-Mail: [email protected]
Any misprints, errors or changes in the description of these operating instructions may occur.