![Schrack Technik AVARA Multi Power Series Advanced Configuration Manual Download Page 18](http://html1.mh-extra.com/html/schrack-technik/avara-multi-power-series/avara-multi-power-series_advanced-configuration-manual_1214346018.webp)
14
M
ODULAR
B
ATTERY CONNECTION CONFIGURATION
There are 3 possible connection types:
•
Shared: with a single battery connection shared by all the UPS Cabinets within the system.
•
Separate: each UPS Cabinet is connected exclusively to one or more Battery Cabinets electrically separated from the
Battery Cabinets connected to the other UPS Cabinets.
•
Groups/Pairs: the UPS Cabinets are grouped into pairs. Each pair has a separate battery source.
NOTES
- The only configuration possible with a single UPS Cabinet is the connection to shared batteries.
- The Pair connection is only permitted where there are 4 UPS Cabinets.
- Following a configuration modification, if the conditions to maintain the selection made are not present, the system
will automatically reset the configuration to shared batteries, issuing a suitable warning message.
WARNING: If internal Battery Unit Arrays are installed within a Combo Cabinet, any additional batteries must
be modular. In this case, additional modular Battery Cabinets will be required.
S
HARED BATTERIES
In the event of Modular Batteries connected in a “shared connection” configuration, no additional configuration is required other
than selecting how many and which Battery Cabinets are present along with the respective BUA.