Operating instructions
Pull-wire emergency-stop switches

ZQ 700 AS

EN

3.2  Dimensions

All measurements in mm

17

30,5

40,5

51

30

40,5

p/M5

M20x1,5

2

60

160

94

B

A

Key

A

Position indication

B

Reset button

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  
authorised personnel in a de-energised condition

The connection to the AS-Interface system is realised through an M12 
connector or an AS-i flat cable clamp The wiring configuration of the 
M12 connector is defined as follows (to EN 50295):

Pin assignment M12 connector

4-pole

3

2

1

4

PIN 1: AS-i +

PIN 2: spare
PIN 3:AS-i -
PIN 4: spare

5.  Functions and configuration

5.1  Programming the slave address

The slave address is programmed through the AS-i connector Any 
address from 1 to 31 can be set by means of the AS-i bus master or a 
hand-held programming device

5.2  Configuration of the safety monitor

The safety switch can be configured in the ASIMON  
configuration software with the following monitoring devices  
(refer to ASIMON manual):

Double channel dependent

• Optionally with startup test

• Synchronisation time typically 0.1 - 0.5 s

The configuration of the safety monitor must be tested and 
confirmed by a qualified and authorised safety expert/safety 
engineer 

5.3  Status signal "safety release"

The "safety release" status signal from a Safety at Work slave can be 
cyclically queried by the control system through the AS-i master To 
thiseffect, the 4 input bits with the varying SaW code of a Safety at 
Work slave are evaluated through an OR operation with 4 inputs in the 
control system

6.  Diagnostic

6.1  Internal LED indications

The LED's have the following meaning (to EN 50295):

LED yellow

Channel 1 / AS-i SaW-Bit 0,1

LED green/red

(AS-i duo LED):

AS-Interface supply voltage/ 
AS-Interface communication error or  
slave address = 0 or periphery error

LED yellow

Channel 2 / AS-i SaW-Bit 2,3

6.2  Read-out of the parameter ports

The parameter port P0 to P3 of an AS-i slave can be read out through 
the control interface of the AS-i master (see component description) by 
using the "Write parameter" instruction (with hexadecimal value F) This 
(non-safe) diagnostic information from the reflected parameters or the 
answer to a "Write parameter instruction" can be used by the user for 
diagnostic purposes or for the control programme

Table 3: diagnostic information (P0 … P3)

Parameter bit

Condition = 1

Condition = 0

0

Channel 2 activated

Channel 2 disabled

1

2

3

Summary of Contents for ZQ 700 AS

Page 1: ...he entire machinery or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual t...

Page 2: ... switching elements have 2 contacts in tensioned condition the NC contacts are closed After actuation of the switching function a latching mechanism main tains the stop command until the switch is released by pushing the blue reset button Prior to the reset of the stop signal the reason why the switch has been actuated must be determined The switch can only be reset if the switch is correctly pre ...

Page 3: ...ibrations in the wire on machines with high vibrations it is recommended to realise the individu al support length differently Assembly refer to image 2 6 4 2 3 6 5 6 1 0 1m 2 5m max 10m 4 6 3 2 A B 9 8 2 3 0 1m 2 5m max 10m 1 8 2 7 A B 3 9 Image 2 mounting of the components Key 1 Pull wire with red PVC sheath Ø 5 mm steel core Ø 3 mm 2 Eyebolt 3 Nut 4 Wire clamp 5 Tensioner 6 Wire thimble 7 Shack...

Page 4: ...ion time typically 0 1 0 5 s The configuration of the safety monitor must be tested and confirmed by a qualified and authorised safety expert safety engineer 5 3 Status signal safety release The safety release status signal from a Safety at Work slave can be cyclically queried by the control system through the AS i master To thiseffect the 4 input bits with the varying SaW code of a Safety at Work...

Page 5: ...ion indicator 7 2 Maintenance A regular visual inspection and functional test including the following steps is recommended 1 Check the functionality of the switch by actuating the wire 2 Check the cable entries and the wire connections 3 Remove particles of dust and soiling 4 Check the wire tension through the wire position indication and check the wire and the wire guides for damages and proper f...

Page 6: ...iver Wacker Möddinghofe 30 42279 Wuppertal 9 Appendix 9 1 EC Declaration of conformity K A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com Place and date of issue Wuppertal September 9 2014 Authorised signature Philip Schmersal Managing Director E...

Reviews: