2
Operating instructions
Pull-wire emergency-stop switches
ZQ 700 AS
EN
1.6 Warning about misuse
In case of improper use or manipulation of the safety switch-
gear, personal hazards or damages to machinery or plant
components cannot be excluded The relevant requirements
of the standard EN ISO 13850 must be observed
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual The manufacturer shall accept no liability for damages result-
ing from the use of unauthorised spare parts or accessories
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modifications
to the device
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
ZQ 700
➀
-AS
No.
Option
Description
➀
ST
Connector plug M 12
FK
Flat cable connection
Only if the information described in this operating instructions
manual are realised correctly, the safety function and there-
fore the compliance with the Machinery Directive is maintained
2.2 Special versions
For special versions, which are not listed in the order code below 21,
these specifications apply accordingly, provided that they correspond to
the standard version
2.3 Destination and use
The emergency stop switch meets the requirements of EN ISO 13850,
IEC/EN 60947-5-1 and IEC/EN 60947-5-5 Pull-wire emergency stop
switches are used on machinery and plants, where triggering the emer-
gency stop command must be enabled at arbitrary points on the wire run
If the tensioned pull-wire is pulled or in case of wire breakage, the
switching function of the pull-wire emergency stop switch is activated
(refer to image 1)
F
1
0
0
Image 1: position indication and actuation
Design/operating principle
The pull-wire emergency stop switches are brought into the operational
condition by the proper pre-tensioning of a maximum 10 m long wire
The inner switching elements have 2 contacts; in tensioned condition,
the NC contacts are closed
After actuation of the switching function, a latching mechanism main-
tains the stop command until the switch is released by pushing the blue
reset button Prior to the reset of the stop signal, the reason why the
switch has been actuated must be determined The switch can only
be reset if the switch is correctly pre-tensioned (position indication in
central position, refer to image 1)
An AS-Interface Safety at Work component functions on the basis of an
individual code generator (8 × 4 bit) This safety code is cyclically trans-
mitted over the AS-i network and monitored by the ASM safety monitor
The component status can be evaluated through a PLC with AS-Inter-
face master The safety-related functions are enabled by means of the
AS-i safety monitor
The user must evaluate and design the safety chain in
accordance with the relevant standards and the required
safety level
2.4 Technical data
Standards:
EN 60947-5-1, EN 60947-5-5, EN ISO 13850,
EN 50295, EN ISO 13849-1, IEC 61508
Enclosure:
glass-fibre reinforced thermoplastic,
self-extinguishing
Cover:
glass-fibre reinforced thermoplastic,
self-extinguishing
Wire length:
max 10 m depending in relation to the
range of ambient temperature (see image 3)
Switching system:
Snap action, positive break NC
Mechanical life:
≥ 100.000 operations
Switching frequency:
max 1/s
Response time:
< 100 ms
Connection:
Connector plug M12, 4-pole or FK
Electrical data - AS-Interface:
AS-i supply voltage:
180 316 VDC, through AS-Interface,
reverse polarity-proof (stabilised PELV unit)
AS-I power consumption:
≤ 0,05 A
AS-i Device insulation:
internal short-circuit proof
AS-I specification:
Version:
V 30
Profile:
S-0BFF
IO-Code:
0×0
ID-Code:
0×B
ID-Code 1:
0×F
ID-Code 2:
0×F
AS-interface inputs:
Channel 1:
DI 0 / DI 1 = dynamic code transmission
Channel 2:
DI 2 / DI 3 = dynamic code transmission
AS-interface outputs:
DO 0 DO 3:
no function
AS-Interface parameter port:
P0:
Channel 2 switched
P1 … P3:
no function
Input module address:
0, preset to address 0,
can be changed through AS-interface bus master
or hand-held programming device
LED switching conditions display (internal)
LED yellow:
Channel 1, SaW-Bit 01
LED green-red (AS-i Duo LED):
AS-Interface supply voltage /
AS-Interface communication
error / slave address = 0
or periphery error detected
LED yellow:
Channel 2, SaW-Bit 23