schmersal TESF series Operating Instructions Manual Download Page 4

4

Operating instructions

Hinge safety switch

TESF

EN

Special instructions for the on-site setting (version TESF.../U)

We recommend a setting including the following steps:

1.  Open the safety guard up to the maximum authorised opening angle.

2.  Open the enclosure cover of the hinge switch.

3.  Wire both NC contacts parallel, connect terminal 11 with 31 and 

terminal 12 with 32 (Fig. 5).

4.  Connect the continuity tester to the terminals 11/12 of the NC con-

tacts or use the test handles at the terminals (Fig. 5).

5.  Use the adjustment tool to set the NC contacts so that their opening 

is ensured at the maximum authorised safety guard opening angle. 

Turn clockwise to decrease the switching angle, turn counterclock-

wise to increase the switching angle (Fig. 6); when mounted inside 

accordingly reversed. The positive break angle is 7° larger than the 

set switching angle.

6.  After the switch is set, the compliance of the switch with the safe-

ty-technical requirements of the application must be checked.

7.  After the switching angle has been set and checked, the blanking 

plug for the adjustment opening located at the rear of the adjustment 

tool must be inserted in the adjustment opening (1) and torn down by 

making lateral movements (2) with the tool (Fig. 7).

After the desired switching point is set, the opening of the set-

ting option imperatively must be sealed with a blanking plug.

This measure prevents tampering at the set switching point 

within the meaning of ISO 14119 paragraph 7 and therefore 

avoids any loss of the safety function of the device.

The blanking plug is injected to the special adjustment tool 

with a predetermined breaking point.

We recommend an additional painting or glueing of the 

blanking plug.

Securing the setting screw by means of the blanking plug is a 

mandatory instruction for the user, which must be oberved in 

order to maintain the CE-Conformity of the component.

bridge

11/31

12/32

Test output

11/12

Fig. 5

+

-

Fig. 6

Fig. 7

The versions TESF.../ST24 must only be used in PELV cir-

cuits according to EN 60204.

4.2  Contact variants

Contacts are shown with safety guard closed.

TESF... / TESF.../CC

11 12 23 24

31 32 43 44

11

12

31

32

23

24

43

44

A

A

TESF... / TESF.../CC

1 2 3 4

11

12

5 6 7 8

31

32

23

24

43

44

A

A

5

8

4

3

2

1

7

6

Accessories

Connecting cable with  

M12 coupling, 8-pole, straight

Type designation

Cable length Ordering code

A-K8P-M12-S-G-2.5M-BK-2-X-A-4
A-K8P-M12-S-G-5M-BK-2-X-A-4
A-K8P-M12-S-G-10M-BK-2-X-A-4
A-K8P-M12-S-G-15M-BK-2-X-A-4

2.5 m
5.0 m

10 m
15 m

103011415

103007358
103007359

103011414

Pin configuration

5

8

4

3

2

1

7

6

1

WH

2

BN

3

GN

4

YE

5

GY

6

PK

7

BU

8

RD

4.3  Switch travel

(10°)

180°

11-12

31-32

43-44

23-24

A

A

Key

A

  Positive break NC contact

T

   Positive break travel / -angle,  

taking tolerances and wear into account

Summary of Contents for TESF series

Page 1: ...e applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further tech...

Page 2: ... be validated to the relevant standards 2 4 Technical data Standards IEC 60947 5 1 BG GS ET 15 Enclosure Zinc diecast enclosure cover self extinguishing thermoplastic Hinge bolt Stainless steel 1 4305 Contact material Silver gold plated Protection class IP65 Contact type Change over contact with double break Zb Switching system A IEC 60947 5 1 slow action NC contact with positive break Connection ...

Page 3: ...41 5 25 5 41 5 22 11 4 TESF TESF S 6 1 100 25 5 25 5 41 5 41 5 75 5 115 4 11 21 5 90 M16x1 5 51 40 6 1 55 51 51 25 5 41 5 25 5 41 5 22 11 4 4 Electrical connection 4 1 General information for electrical connection The electrical connection may only be carried out by authorised personnel in a de energised condition For the cable entry only suitable cable glands and for the connector suitable plugs ...

Page 4: ...nt is set the opening of the set ting option imperatively must be sealed with a blanking plug This measure prevents tampering at the set switching point within the meaning of ISO 14119 paragraph 7 and therefore avoids any loss of the safety function of the device The blanking plug is injected to the special adjustment tool with a predetermined breaking point We recommend an additional painting or ...

Page 5: ...26 7 251 7 1 500 78 5 104 6 130 7 156 7 182 7 208 7 234 5 260 3 β Door opening angle C Door width in mm D Door gap in mm for overlapping B 0 mm B Door thickness Calculation example The actual door gap D1 is calculated using door gap D calculated by means of the table above minus the overlapping B of door and frame D1 D B Example A door made of 40 mm aluminium profile with a length of 950 mm should...

Page 6: ...Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com Place and date of issue Wuppertal January 2 2017 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Interne...

Reviews: