TESF

Operating instructions

Hinge safety switch

EN

3.  Mounting

3.1  General mounting instructions

During fitting of the actuator and the sensor, the requirements 

of ISO 14119, especially paragraph 7 must be observed!

Four mounting holes are provided for fixing the switch. When used in 

applications with function for the protection of man, the components 

must be fitted so that disassembly is prevented (e.g. drill out the hexag-

onal recess of the fixing screws, blocking the hexagonal recess using a 

plastic cone diamater 5.1 mm). The hinge switch furthermore must be 

pinned after assembly and adjustment (Fig. 1). The hinge safety switch 

must not be used as an end stop. Any mounting position. The mounting 

position however is chosen so that the components are preferably fitted 

in the upper part of the safety guard to avoid the ingress of dirt and soil-

ing as well as damage to the components. In case of painting activities, 

the components must be covered.  The supplied fixing material must 

be used. We recommend that the fixing screws are painted after the 

component is fitted.

II

II

A)

Fig. 1

Legend:

A = Drill and pin in this area

Please observe the remarks of the standards ISO 12100, 

EN 953 and ISO 14119. Also observe the safety distances 

to the standards ISO 13857 and EN 349.

3.2  Dimensions

All measurements in mm.

TESFA

TESFA/S

6.1

100

25.5

25.5

41.5

41.5

75.5

115

90

M16x1,5

51

4

11

21.5

40

6.1

55

51

51

25.5

41.5

25.5

41.5

22

11

4

TESF

TESF/S

6.1

100

25.5

25.5

41.5

41.5

75.5

115

4 11

21.5

90

M16x1,5

51

40

6.1

55

51

51

25.5

41.5

25.5

41.5

22

11

4

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition. For the 

cable entry, only suitable cable glands and for the connector 

suitable plugs with an appropriate degree of protection must 

be used.

1.  Open the enclosure cover of the hinge switch.

2.  Connect the wires and cables. For flexible leads, conductor ferrules 

must be used. In the area of the metal thread at the cable input in the 

wiring compartment, the supplied protective tube (shrink tube) must 

be used.

3.  After the switch has been fitted, the switching function and the open-

ing angle of the safety guard must be checked. The switching angle 

of the NC contacts set in factory is approximately 3°. Caution: for the 

TESF.../U version, the following paragraph "Special instructions for 

the on-site setting" imperatively must be observed!

4.  Follow the steps below to put back the enclosure cover:

  –  Firmly push the enclosure cover under an angle of approx. 30° 

onto the retaining collar (Fig. 2) and simultaneously exercise a 

downwards pressure (Fig. 3).

  –  Uniformly tighten the 3 cover screws (Fig. 4) with 0.6 Nm tighten-

ing torque.

  –  The contact labelling can be found in the wiring compartment of 

the switch.

30°

F

Fig. 2

Fig. 3

F

Fig. 4

After the switch has been fitted, the switching function and the opening 

angle of the safety guard must be checked. The opening angle of the 

NC contacts set in factory is approximately 3°.

Summary of Contents for TESF series

Page 1: ...e applications authorised by the manufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further tech...

Page 2: ... be validated to the relevant standards 2 4 Technical data Standards IEC 60947 5 1 BG GS ET 15 Enclosure Zinc diecast enclosure cover self extinguishing thermoplastic Hinge bolt Stainless steel 1 4305 Contact material Silver gold plated Protection class IP65 Contact type Change over contact with double break Zb Switching system A IEC 60947 5 1 slow action NC contact with positive break Connection ...

Page 3: ...41 5 25 5 41 5 22 11 4 TESF TESF S 6 1 100 25 5 25 5 41 5 41 5 75 5 115 4 11 21 5 90 M16x1 5 51 40 6 1 55 51 51 25 5 41 5 25 5 41 5 22 11 4 4 Electrical connection 4 1 General information for electrical connection The electrical connection may only be carried out by authorised personnel in a de energised condition For the cable entry only suitable cable glands and for the connector suitable plugs ...

Page 4: ...nt is set the opening of the set ting option imperatively must be sealed with a blanking plug This measure prevents tampering at the set switching point within the meaning of ISO 14119 paragraph 7 and therefore avoids any loss of the safety function of the device The blanking plug is injected to the special adjustment tool with a predetermined breaking point We recommend an additional painting or ...

Page 5: ...26 7 251 7 1 500 78 5 104 6 130 7 156 7 182 7 208 7 234 5 260 3 β Door opening angle C Door width in mm D Door gap in mm for overlapping B 0 mm B Door thickness Calculation example The actual door gap D1 is calculated using door gap D calculated by means of the table above minus the overlapping B of door and frame D1 D B Example A door made of 40 mm aluminium profile with a length of 950 mm should...

Page 6: ...Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com Place and date of issue Wuppertal January 2 2017 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Interne...

Reviews: