schmersal SRB301HC/T-24V Operating Instructions Manual Download Page 3

3

SRB301HC/T-24V

SRB301HC/T-230V

Operating instructions
Safety-monitoring module

EN

Switching capacity of the safety contacts: 

13-14; 23-24; 33-34: 

max. 250 V, 8 A ohmic (inductive in case  

of appropriate protective wiring);  

min. 10 V / 10 mA

Switching capacity of the auxiliary contacts:

 

41-42: 24 VDC / 2 A

Protection of the safety contacts

 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 10 A quick blow, 8 A slow blow

Fuse rating for the auxiliary contacts: 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 2.5 A quick blow, 2 A slow blow

Current and voltage at the control circuits: 

 

- S13-S14: 

24 VDC, start impulse: 80 mA / 120 ms;  

continuous current: 20 mA 

- S23-S24:

 

24 VDC / 20 mA 

- X1-X2: 

24 VDC, start impulse: 80 mA / 120 ms

Utilisation category to EN 60947-5-1:

 

AC-15: 230 V / 3 A  

DC-13: 24 V / 2 A

Dimensions (H/W/D):  

100 mm x 45 mm x 121 mm

The data specified in this manual are applicable when the  

component is operated with rated operating voltage U

e

 ±0%.

2.5   Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value:

 

≤ 2,00 × 10

-8

/

h

SIL:

 

up to 3

Service life: 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching cy-
cles (n

op/y

) mentioned in the table below. At 365 operating days per year 

and a 24-hours operation, this results in the below-mentioned switching 
cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 
and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 45 x 121 mm

with plugged-in terminals: 120 × 45 × 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 
against unintentional contact of the connected and therefore 
electrically interconnected apparatus and the insulation of the 
feed cables must be designed for the highest voltage, which 
can occur in the device.

The electrical connection may only be carried out by  
authorised personnel in a de-energised condition.

Wiring examples: see appendix

To avoid EMC disturbances, the physical ambient and opera-
tional conditions at the place where the product is installed, 
must meet the provisions laid down in the paragraph "Electro-
magnetic Compatibility (EMC)" of DIN EN 60204-1.

5.  Operating principle and settings

5.1  LED functions

•  ON: supply voltage is on. / OFF: supply voltage missing, short-circuit 

between inputs S13-S14, S23-S24, internal power supply error

•  IN A: ON: input S13-S14 closed / OFF: input S13-S14 open or wire 

breakage

•  IN B: ON: input S23-S24 closed / OFF: input S23-S24 open or wire 

breakage

•  OUT: ON: both internal relays are interconnected, when S13-S14 and 

S23-S24 are closed and the feedback circuit is closed /  
OFF: when the inputs S13-S14 or S23-S24 or the feedback circuit  
are/is not closed

5.2  Description of the terminals

Voltages:

A1

A2

+24 VDC / 24 VAC / 48 … 230 VAC

0 VDC / 0 VAC

Inputs:

S13-S14

S23-S24

Input channel 1 (+)

Input channel 2 (-)

Outputs:

13-14

23-24

33-34

41-42

First safety enabling circuit (stop 0)

Second safety enabling circuit (STOP 0)

Third safety enabling circuit (stop 0)

Auxiliary NC contact as signalling contact

Feedback 

circuit:

X1-X2

Start:

X1-X2

Manual start (reset button)

5.3  Notes

Signalling outputs must not be used in safety circuits.

ON
IN A
IN B
OUT

A1 S13 S24 X1

A2 S14 S23 X2

41

23

13

33

42

24

14

34

SRB 301HC/T

...V

Fig. 1