schmersal SRB 301ST-230V Operating Instructions Manual Download Page 3

3

SRB 301ST-230V

Operating instructions

Safety-monitoring module

EN

Fuse rating of the safety contacts:

 

 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 8 A quick blow, 6 A slow blow

Fuse rating for the auxiliary contacts: 

 

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 2.5 A quick blow, 2 A slow blow

Utilisation category to EN 60947-5-1:

 

AC-15: 230 VAC / 6 A  

DC-13: 24 VDC / 6 A

Dimensions H x W x D:

 

100 mm x 22.5 mm x 121 mm

The data specified in this manual are applicable when the component is 

operated with rated operating voltage U

e

 ±0%.

2.5  Safety classification

Standards: 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL: 

up to e

Control category: 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value: 

≤ 2.00 × 10

-8

/h

SIL: 

up to 3

Service life: 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching 

cycles (n

op/y

) mentioned in the table below. At 365 operating days per 

year and a 24-hours operation, this results in the below-mentioned 

switching cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

with plugged-in terminals: 120 × 22.5 × 121 mm

4.  Rear side Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

• K1: Status channel 1

• K2: Status channel 2

•   U

i

:  Status internal operating voltage (LED is on, when the operating 

voltage on the terminals A1-A2 is ON and the fuse has not been 

triggered).

5.2  Description of the terminals

Voltages:

A1
A2

48 … 240 VAC
48 … 240 VAC

Inputs:

S11-S12
S21-S22

Input channel 1 (+)
Input channel 2 (+)

Outputs:

13-14
23-24
33-34
41-42

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit
Auxiliary NC contact

Start:

X2
X3

Feedback circuit and external reset
Feedback circuit and automatic start

U

i

K1

K2

X2 S12 S11 A1

33 23 13 41

SRB

301ST

-230V

X3 S22 S21 A2

34 24 14 42

Fig. 1

5.3  Notes

Signalling outputs must not be used in safety circuits.

Due to the operating principle of the electronic fuse, the 

customer must check that no hazard is caused by an 

unexpected restart in circuits without reset button (automatic 

start).