8.3  Sensor configuration

Dual-channel control of a safety-related electronic (microprocessor- 

based) safety guard with p-type transistor outputs e.g. AOPD's  

to EN IEC 61496 (see Fig. 10)

•  Wire breakage and earth leakage in the control circuits are detected.

•  The safety-monitoring module therefore is not equipped with a cross-

wire short detection here. The safety-monitoring module therefore is 

not equipped with a cross-wire short detection here.

•  Control category: 3 to EN 954-1

•  If cross-wire shorts in the control circuits are detected by the  

safety guard:  

- control category 4 to EN 954-1  

- category 4 – PL e to DIN EN ISO 13 849-1 possible.

Single-channel emergency stop circuit with command devices to 

DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 11)

•  Wire breakage and earth le akage in the control circuits are detected.

•  Control category: 2 to EN 954-1

•  Category 2 – PL d to DIN EN 13849-1 possible

Dual-channel emergency stop circuit with command devices to 

DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 12)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Control category: 3 to EN 954-1

•  Category 4 – PL e to DIN EN ISO 13849-1 possible  

(with protective wiring)

S12

+24V

S32

+24V

S22

S21

S12

S11

S32

S31

S22

S21

S12

S11

S32

S11

S22

S21

Fig. 10

Fig. 11

Fig. 12

Dual-channel emergency stop circuit with command devices to 

DIN EN ISO 13850 (EN 418) and EN 60947-5-5 (Fig. 13)

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

•  Control category: 4 to EN 954-1

•  Category 4 – PL e to DIN EN ISO 13849-1 possible.

Single-channel guard door monitoring circuit with interlocking 

devices to EN 1088 (Fig. 14)

•  At least one contact with positive break required.

•  Wire breakage and earth le akage in the control circuits are detected.

•  Control category: 2 to EN 954-1

•  Category 2 – PL d to DIN EN ISO 13849-1 possible.

Dual-channel guard door monitoring circuit with interlocking 

device to EN 1088 (see Fig. 15)

•  With at least one positive-break position switch

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are not detected.

•  Control category: 3 to EN 954-1

•  Category 4 – PL e to DIN EN ISO 13849-1 possible  

(with protective wiring)

S32

S31

S22

S21

S12

S11

S12

S11

S32

S31

S22

S21

S12

S11

S32

S11

S22

S21

Fig. 13

Fig. 14

Fig. 15

Dual-channel guard door monitoring circuit with interlocking 

device to EN 1088 (see Fig. 16)

•  With at least one positive-break position switch

•  Wire breakage and earth leakage in the control circuits are detected.

•  Cross-wire shorts between the control circuits are detected.

•  Control category: 4 to EN 954-1

•  Category 4 – PL e to DIN EN 13849-1 possible

Monitored dual-channel safety guard: dual-channel safety guard 

monitoring to EN 1088 with at least one positive-break position 

switch and automatic start (Fig. 17)

•  This control system recognises wire breakage and earth faults in the 

guard monitoring circuits.

•  Cross-wire shorts between the guard monitoring circuits are detected.

•  A time of approx. 500 ms is tolerated between the opening of the 

contacts S13-S14 and the closing of S21-S22 and S31-S32.

•  Category 4 – PL e to DIN EN 13849-1 possible

S32

S31

S22

S21

S12

S11

S22

S21

S32

S31

S14

S13

S12

S11

Fig. 16

Fig. 17

Summary of Contents for SRB 220XV2 V.2

Page 1: ...versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description To avoid EMC dist...

Page 2: ...th the output contacts 13 14 and 23 24 meet the following requirements under observation of a B10D value assessment also refer to Requirements to DIN EN ISO 13849 1 control category 4 PL e to DIN EN I...

Page 3: ...results in the below mentioned switching cycle times tcycle for the relay contacts Diverging applications upon request Contact load nop y tcycle 20 525 600 1 0 min 40 210 240 2 5 min 60 75 087 7 0 min...

Page 4: ...saved in the SRB 220XV2 the voltage supply must be interrupted for approx 3 seconds ON ON SW1 SW2 1 1 2 2 3 3 4 4 Fig 3 New adjustable drop out delays and cross wire short monitoring for version V 2...

Page 5: ...iptions and legislations 8 Appendix 8 1 Wiring examples Dual channel control shown for a guard door monitor with two contacts A and B where at least one is a positive break contact with external reset...

Page 6: ...s between the control circuits are detected Control category 4 to EN 954 1 Category 4 PL e to DIN EN ISO 13849 1 possible Single channel guard door monitoring circuit with interlocking devices to EN 1...

Page 7: ...s S feedback circuit If the feedback circuit is not required establish a bridge S33 S34 47 13 48 14 KB KA S L1 N KA KC S33 S34 47 13 48 14 KB KC KD KA KB L1 N KA KD KC S Fig 18 Fig 19 Differential con...

Page 8: ...omponent SRB220XV2 V 2 Description of the component Safety monitoring module for emergency stop circuits and guard door monitoring Relevant Directives Machinery Directive EMC Directive RoHS Directive...

Reviews: