SLG 425I

Operating instructions

Safety light grid

Multiple interruption of the protection field during the muting cycle

This function increases the availability of the system in case of different 

material qualities on one pallet.

Without the function "multiple interruption of the protection field", the 

protection field is monitored during the active muting cycle and any non-

actuation (no beam interrupted) immediately cancels the muting cycle. 

This error function is triggered when all active beams of the protec-

tion field are not actuated for a period of time of over 20 ms e.g. due 

to an irregular loading of the material on the carrier. If the function is 

activated, no shutdown is triggered if the beams are not actuated during 

the muting cycle. The correct termination is realised by the configura-

tion or the muting sensors. The combination with the parameter setting 

"reduced muting cycle" is not possible. These restrictions are marked in 

the software and must be observed.

Activating the protection field

During a muting cycle, the entire protection field height of the SLG 425I 

is bridged. This causes the risk that persons located on or beside the 

material can get into the hazardous area.

The risk can be avoided by activating the remainder of the protection 

field, if the conveyed material has a throughout identical height. In this 

way, the presence of persons within the active protection field height is 

detected!

Procedure:

Position the material onto the carrier so that the protection field of 

the SLG 425I is actuated. If the material height is slightly varying, the 

carrier can be slightly increased during the teaching process to avoid 

false triggering. Now activate the teach sample field in the software. 

The menu automatically switches to the beam view. The beams inter-

rupted by the material are represented in red. The teaching process is 

terminated with a mouse click on the "teach" field. You will return to the 

main menu "muting".

Changing the protection field area

If the protection field height parameterised by means of the teach 

process needs to be changed, the saved value must be deleted and 

reparameterised.

Procedure:

Activating the entire protection field (the previous value is deleted)

Activating the teach sample (change to beam view)

Saving the new value (teach process) with teach

Mounting: 

The first light beam (near the diagnostic window) must not be 

interrupted! I.e. observe the downward cable connection.

2.9.6 Saving the data

After the reconfiguration, the data to be saved are prepared by select-

ing the button "Save settings". To avoid any unintentional saving of 

data, every intentional saving process must be confirmed within 10 

seconds by clicking on the button "Confirm with this button within 10 

seconds".

If it is not confirmed within this timeframe, the settings that were saved 

before the change was made will be maintained without any change.

After the data transmission, the following confirmation is displayed. You 

are simultaneously asked to save the configuration data in the form of 

a text file.

This saving procedure is recommended so that configuration changes 

can be reproduced at a later moment. Click the (yes) button with your 

mouse to confirm.

You now can save the configuration setting onto your PC or laptop.

2.9.7 Muting applications

Arrangement of the muting sensors

MS1

MS2

MS3

MS4

Material

Muting lamp

Belt

Reflektor
Muting Sensor

SLC 425I-E/R

Reflector
Muting sensor
SLG 425I-E/R

MS1 MS2

MS3 MS4

S

E

S3

S2

S1

S1

S2

Material

Carrier

Belt

SF 

= Protection field

S1 

= distance of the inner MS to SF

S2 

= distance between two MS

S3 

= material length

MS 1 

= Muting sensor 1

MS 2 

= Muting sensor 2

MS 3 

= Muting sensor 3

MS 4 

= Muting sensor 4

= Transmitter

= Receiver

Minimum distances muting sensors

For the evaluation of the signals (MS) in the control system, a minimum 

distance is required for the muting sensors.

The minimum signal length between the sensors, which are fitted 

closest to the SLG 425I, must be at least 50 ms. This corresponds to a 

minimum distance of 100 mm at a belt speed of 2.0 m/s.

The minimum signal length of the outer sensors must exceed 50 ms. 

The signal running time between the muting sensors must be 3 sec-

onds at the most (depending on the chosen setting).

Summary of Contents for SLG 425I Series

Page 1: ...unctions Warning Failure to comply with this warning notice could lead to physical injury and or damage to the machine 1 4 Appropriate use The products described in these operating instructions are de...

Page 2: ...on of hazardous points hazardous areas and machine accesses If one or more light beams are interrupted the hazardous movement must be stopped The user must evaluate and design the safety chain in ac c...

Page 3: ...o e Control category up to 4 PFH value 7 42 x 10 9 h SIL up to 3 Service life 20 years 2 8 Functions The system consists of a receiver and a transmitter For the described functions no further switchin...

Page 4: ...beam interruptions The blanking of beams is not authorised for an SLG 425I with 2 beams The blanking of one beam at the most in the SLG 425I 3 beam version or the SLG 425I 4 beam version is au thorise...

Page 5: ...ive 2 9 2 Muting sensors MS The MS muting sensor can be a mechanical capacitive inductive or optoelectronic sensor They have no particular requirements as fail safety is regarded The set up must be ex...

Page 6: ...roup The muting cycle is cancelled when MS 3 second sensor group is no longer actuated 2 9 5 Configuration of the muting function The parameters for the muting mode are set by means of the PC soft war...

Page 7: ...ion The simultaneity of the sensors can be set between 1 to 3 seconds Setting the special functions is recommended In this way the protective function and the availability of the muting application is...

Page 8: ...eld height parameterised by means of the teach process needs to be changed the saved value must be deleted and reparameterised Procedure Activating the entire protection field the previous value is de...

Page 9: ...ld area Factory setting reduced muting cycle i e the muting cycle is terminated when the protection field is released This arrangement is only authorised when the muting sensors are installed inside t...

Page 10: ...SLG must not be exposed to inflammable or explosive gasses The connecting cables must be connected in accordance with the installation instructions The fixing screws of the end caps and the mounting...

Page 11: ...rdous point Transmitter Receiver Command device Authorised operation Mechanical protection Direction from which the hazardous area is accessed The formulae and calculation examples are related to the...

Page 12: ...r and slotted hole centre short end cap L2 Mounting distance mm between floor and slotted hole centre diagnostic window All measurements 1 mm SLG425I ER 0800 03 RF 3 beam version A B C L2 L1 Trans mit...

Page 13: ...Legend A Beam distance B Mounting dimension C Total length L1 Mounting distance mm between floor and slotted hole centre short end cap L2 Mounting distance mm between floor and slotted hole centre di...

Page 14: ...or connection with 2 muting sensors with 4 muting sensors Bridge 1 Restart interlock manual reset active bridge between DIAG OUT and DIAG IN Legend K1 K2 Relay for processing the switching outputs OSS...

Page 15: ...s listed in the chapter Fault diagnostic 5 2 Maintenance Do not use the SLG before the next inspection is terminated An incorrect inspection can lead to serious and mortal inju ries Conditions For saf...

Page 16: ...field Transmitting orange Transmitter active Status green Function display beam coding Receiver LED Status LED Description OSSD ON ON Protection field clear Flashing Diagnostic mode active OSSD OFF ON...

Page 17: ...i e locking Check the configuration settings by means of the NSR 0801 BUS converter repeat the teach process with blanking 6 3 Extended diagnostic By means of the optional configuration software and t...

Page 18: ...30 42279 Wuppertal Notified body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC test certificate n 44 205 10 555867 005 Safety Control GmbH Am Industriepark 33 D...

Reviews: