4
Operating instructions
Safety light curtain / safety light grid
SLC440 Series
SLG440 Series
EN
2.7 Response time (reaction time)
The response time depends on the height of the protection field, the
resolution, the number of light beams and the beam coding A
SLC440
Resolution 14 mm
Protection
field height
[mm]
Beams
(Lines)
[Number]
Response
time
[ms]
Response time
with Beam coding
A
[ms]
Weight
[kg]
170
16
10
15
04
250
24
10
15
05
330
32
10
15
06
410
40
10
15
08
490
48
10
15
09
570
56
20
27
10
650
64
20
27
11
730
72
20
27
12
810
80
20
27
14
890
88
20
27
15
970
96
20
27
16
1050
104
20
27
17
1130
112
20
27
18
1210
120
20
27
20
1290
128
20
27
21
1370
136
20
27
22
1450
144
20
27
23
1530
152
28
40
24
1610
160
28
40
26
1690
168
28
40
27
1770
176
28
40
28
1850
184
28
40
29
1930
192
28
40
30
SLC440
Resolution 30 mm
Protection
field height
[mm]
Beams
(Lines)
[Number]
Response
time
[ms]
Response time
with Beam coding
A
[ms]
Weight
[kg]
170
8
10
15
04
250
12
10
15
05
330
16
10
15
06
410
20
10
15
08
490
24
10
15
09
570
28
10
15
10
650
32
10
15
11
730
36
10
15
12
810
40
10
15
14
890
44
10
15
15
970
48
10
15
16
1050
52
20
27
17
1130
56
20
27
18
1210
60
20
27
20
1290
64
20
27
21
1370
68
20
27
22
1450
72
20
27
23
1530
76
20
27
24
1610
80
20
27
26
1690
84
20
27
27
1770
88
20
27
28
1850
92
20
27
29
1930
96
20
27
30
SLG440
Beams
(Lines)
[Number]
Beam
distance
[ms]
Response
time
[ms]
Response time
with beam
coding A [ms]
Weight
[kg]
2
500
10
15
09
3
400
10
15
135
4
300
10
15
15
2.8 Safety classification
Standards:
ISO 13849-1, EN 62061
PL:
up to e
Control category:
up to 4
PFH value:
514 x 10
-9
/ h
SIL:
up to 3
Mission time:
20 years
2.9 Functions
The system consists of a receiver and an emitter For the described
functions, no further switching elements are requiredThe diagnostic
and function selection takes place with a command device (key
release), refer to the chapter on parameterisation
The system has the following features:
• Protective mode automatic
(automatic start after release of the protection zone)
• Restart Interlock (manual reset)
• Double acknowledgement/reset
• Contactor control (EDM)
• Beam coding A
• Blanking of fixed protection field areas
• Blanking of fixed protection field areas with movable edge region
• Blanking of movable protection field areas
Factory setting
The system features many functions without needing any additional
devices The following table gives an overview of the possible functions
and the factory settings configuration
Function
Factory set-
ting
Configuration
Protective mode,
automatic
not active
External wiring
Restart interlock (ma-
nual reset)
not active
External wiring
Double acknowledge-
ment/reset
not active
with command device
Blanking fixed/floating not active
with command device
Contactor control
(EDM)
not active
with command device
Beam coding A
not active
with command device
By default neither the restart interlock (manual reset) nor
the protective mode is active One of both operating modes
must be wired in order to enable the OSSD outputs If no
operating mode is selected, the following message is shown:
Status indication E1 + LED OSSD OFF (red)