schmersal RSS260 AS Operating Instructions Manual Download Page 6

6

Operating instructions

Safety sensor

RSS260 AS

EN

6.  Diagnostic

6.1  LED indications

The LED's have the following meaning (to DIN EN 62026-2):

LED green-red 

(AS-i Duo LED):

AS-Interface supply voltage /  

AS-Interface communication error /  

Slave address = 0 /  

Periphery error detected /  

Enabling inhibit (tamper protection time) active

Yellow LED:

Device status (enabling status) /  

hysteresis signal / device error

6.2  Error

Errors, which no longer guarantee the safe functionality of the  

RSS260 AS electromagnetic interlock, cause the safety outputs to be 

switched off and are signaled through a flashing pattern of the red LED. 

(see table 2).

After fault rectification, the error message can be reset by opening and 

closing the relevant guard door. The safety outputs of the safety monitor 

can be switched back on, thus enabling the machine. 

6.3  Diagnostic information

Table 1: Diagnostic information of the RSS260 AS safety switchgear

The safety switch signals the operational state as well as errors through three coloured LED’s installed on the device.

System condition

LED

Periphery error

Reset

green-red

yellow

AS-i SaW-Code

AS-i duo-LED

Status

FID-Bit

(DI 0 ... DI 3)

Safety guard open

green

Off

0

static 0

Guard door closed

green

on

0

dynamically (authorised operation)

Actuated in limit area

red-green flashing Flashes

1

dynamically (authorised operation)

Enabling inhibit (tamper protection time) active red-green flashing Off

1

static 0

Internal device error / periphery error

red-green flashing Flashes 

1)

1

static 0

AS-i error: slave address = 0 
or communication error

red

depending on 
the condition

0

static 0

1) refer to flash code

Table 2: Error messages / flash codes yellow LED

Flash codes (yellow)

Designation

Autonomous  

switch-off after

Error cause

4 flash pulses

Ambient temperature high

0 min

Ambient temperature too high: T > 60 °C

5 flash pulses

Actuator fault

0 min

incorrect or defective actuator

yellow permanent light

Internal error

0 min

Device defective

6.4  Diagnostic signal periphery error

All error messages of the safety switchgear are also transmitted as a 

"periphery error" to the control system through the AS-i master.

A "periphery error" (FID input of the AS-i chip) is signaled by the 

alternating red and green flashing of the AS-i duo LED on the AS-i 

device.

6.5  Read-out of the parameter port

The parameter port P0 to P3 of an AS-i slave can be read out through 

the control interface of the AS-i master (see component description) by 

means of the "Write parameter" instruction (with hexadecimal value F). 

This (non-safe) diagnostic information from the reflected parameters or 

the answer to a "Write parameter instruction" can be used by the user 

for diagnostic purposes or for the control programme.

Diagnostic information (P0 … P3)

Parameter bit Condition = 1

0

Actuator in

1

Hysteresis signal (FID)

2

Enabling inhibit (tamper protection time) active (FID)

3

Internal device error detected (FID)

Variant with actuator detection (AD) P0 - P3

Parameter bit Condition = 1

0 … 3

Binary number actuator 01 - 15  
0 = no actuator detected

Summary of Contents for RSS260 AS

Page 1: ... as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the cha...

Page 2: ...rrespond to the standard version 2 3 Comprehensive quality insurance to 2006 42 EC Schmersal is a certified company to appendix X of the Machinery Directive As a result Schmersal is entitled to autonomously conduct the conformity assessment procedure for the products listed in Appendix IV of the MD without involving a notified body The prototype test certificates are available upon request or can ...

Page 3: ...61508 PL e Control Category 4 PFH 3 93 x 10 10 h PFD 6 89 x 10 5 SIL suitable for SIL 3 applications Service life 20 years 3 Mounting 3 1 General mounting instructions During fitting the requirements of ISO 14119 must be observed The mounting holes provide for a variable mounting by means of M4 screws max tightening torque 0 8 Nm The component can be mounted in any position The minimum bend radius...

Page 4: ...sensor side 3 5 Switching distance The side allows for a maximum height misalignment X of sensor and actuator of 8 mm e g mounting tolerance or due to guard door sagging The axial misalignment Y is max 18 mm Y X Actuating curves The actuating curves represent the typical switching distance of the safety sensor during the approach of the actuator subject to the actuating direction Transverse misali...

Page 5: ...ect the 4 input bits with the varying SaW code of a Safety at Work slave are evaluated through an OR operation with 4 inputs in the control system 5 4 Actuator teaching actuator detection Safety sensors with standard coding are ready to use upon delivery Individually coded safety sensors and actuators will require the following teach in procedure 1 Switch the safety sensor s voltage supply off and...

Page 6: ...ng Off 1 static 0 Internal device error periphery error red green flashing Flashes 1 1 static 0 AS i error slave address 0 or communication error red depending on the condition 0 static 0 1 refer to flash code Table 2 Error messages flash codes yellow LED Flash codes yellow Designation Autonomous switch off after Error cause 4 flash pulses Ambient temperature high 0 min Ambient temperature too hig...

Page 7: ...nctionality A regular visual inspection and functional test including the following steps is recommended 1 Check the safety function 2 Check the fixing and integrity of the safety switchgear the actuator and the cable 3 Remove possible metal chips Measures must be taken to protect against manipulation or against the bypassing of safety device for example using an extra actuator Damaged or defectiv...

Page 8: ...t Directives Machinery Directive RED Directive RoHS Directive 2006 42 EC 2014 53 EU 2011 65 EU Applied standards EN 60947 5 3 2013 EN 300 330 V2 1 1 2017 ISO 14119 2013 EN ISO 13849 1 2008 AC 2009 IEC 61508 parts 1 7 2010 EN 62061 2005 AC 2010 A1 2013 Notified body for the prototype test TÜV Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype test certificate 01 205 5...

Reviews: