PROTECT SELECT

PROTECT SELECT OEM

Operating instructions

Multifunctional safety controller

EN

2.4  Technical data

General data 

Standards:

 

EN 60204-1 ; EN 60947-5-1; EN 62061;  

ISO 13849-1; IEC 61508

Mounting:

 

snaps onto standard DIN rail to EN 60715

Dimensions (W/H/D):

 

52.5 x 100 x 118 mm

Weight:

 

300 g

Readiness after switching on: 

 

approx. 6 s

Mechanical data 

Terminal types:

  

Spring force terminals or screw terminals

Cable section:

 

0.25...2.5 mm²

Connecting cable:

 

rigid or flexible (including conductor ferrules)

Mechanical life:

 10

7

 operations

Electrical life: 

 

Derating curve available on request

Resistance to shock:

 

to IEC 60068-2-29

Resistance to vibrations:

 

to IEC 60068-2-6

Ambient conditions 

Ambient temperature:

 

−25 °C … +55 °C,  

no condensation;  

with vertical installed position

Storage and transport temperature:

 

−25 °C … +75 °C,  

no condensation

Climatic conditions:

 

Humidity 15 % … 90 %,  

no condensation

Protection class:

 IP20

Installation compartment:

 

earthed, lockable switch cabinet 

 with class of protection IP54

Air clearances and creepage distances:

  EN 50178 (double insulation)

EMC rating:

 

EN 61000-6-2; EN 61496-1;  

EN 62061; IEC 61326-3-1

EMC interference radiation:

 

EN 61000-6-4

Overvoltage category:

 III

Degree of pollution:

 2

Electrical data 

Rated operating voltage:

 

24 VDC +/− 10%

Fuse rating:

 

3 A slow blow external

Power consumption at 24 VDC:

 

max. 500 mA, internally  

fused plus load current

Safe digital inputs 

Number:

 

18 single channel / up to 9 dual channel inputs

Voltage / current:

 

24 V; 6 mA

Level (nominal): 

 

- Low:

 

−3 V … 2.0 V 

- High:

 

18 V … 28.8 V

Category / PL / SIL CL: 

 

- Single channel, with minimum 

 

  Request interval = 30 h: 

Cat. 2 / PL d / SIL CL 2 

- Dual channel: 

Cat. 4 / PL e / SIL CL 3

Safe analogue inputs 

Number:

 2

Measuring range voltage:

 

0 … 10 V

Voltage change:

 

Sinusoidal: max. 2.8 Hz; max. 25 V/s

Measuring range current: 

 

- with external shunt resistor:

 

0 … 20 mA 

- 500 Ω / 0.5W / < 1%:

 

4 … 20 mA

Current change:

 

Sinusoidal: max. 2.8 Hz; max. 50 mA/s

Input resistance:

 

10 kΩ

Safe analogue inputs 

Category / PL / SIL CL: 

 

- Single channel (If a cable break dominates):

  Cat. 3 / PL d / SIL CL 2 

- Dual channel:

 

Cat. 4 / PL e / SIL CL 3

Accuracy:

 3%

Resolution:

 

12 Bit

Safe semi-conductor outputs 

Number (p-/n-switching):

 2 

- Note:

 

with OEM -version an activation of the second  

p+n-switching output Q1/Q1N is possible.  

In this case a derating must be observed.

Number (p switching):

 2

Max. current at 24V: 

 

0.7 A / output, resistive load,  

short-circuit proof

Output teat pulse:

 

type 0.5 ms; max. 2 ms,  

with a capacitive load

Category / PL / SIL CL: 

 

- Single channel, with minimum 

 

  Request interval = 47min: 

Cat. 2 / PL d / SIL CL 2 

- Dual channel: 

Cat. 4 / PL e / SIL CL 3

Reaction times: 

  

- Digital inputs:

 

Switching off: < 30 ms 

Switching on: < 45 ms 

- Analogue inputs:

 

Switching off: < 100 ms 

Switching on: < 120 ms 

- Note:

 

The stable time must be added to the specified ON times.

Voltage drop: 

 

- Residual current:

 

< 1 V, < 2 mA 

- Leakage current in the case of error:

 

< 1 mA

Minimum operating current:

 

> 5 mA

Required short-circuit current:

 

9 A

Safe relay outputs 

Number: 

 

2 (common access)

Contact load capacity (B

10d

 values see below): 

 

- AC1:

 

250 V / 4 A 

- AC15:

 

230 V / 3 A 

- DC 1:

 

24 V / 4 A 

- DC 13:

 

24 V / 4 A / 0.1 Hz

Category / PL / SIL CL: 

 

- Single channel:

 

Cat. 1 / PL c / SIL CL 1 

- Dual channel:

 

Cat. 4 / PL e / SIL CL 3

Residual current at 24V:

 

4 A

Fuse rating:

 

4A gL/gG (for residual current)

Reaction times: 

  

- Digital inputs:

 

Switching off: < 50 ms 

Switching on: < 65 ms 

- Analogue inputs:

 

Switching off: < 120 ms 

Switching on: < 140 ms 

- Note:

 

The stable time must be added to the specified ON times.

Required short-circuit current:

 

1000 A to EN 60947-5-1

Rated isolated voltage:

 

to EN 50178, double insulation

Signalling outputs 

Number, optional:

 4

Max. current at24V:

 

0.1 A, resistive load,  

conditionally short-circuit proof

Test pulse outputs 

Number:

 3

Max. current at24V:

 

0.1 A, resistive load,  

conditionally short-circuit proof

Switch-off test pulse:

 

<1.5 ms

cULus 

LISTED 382E

Main supply:

 

24 V, Class 2

Consumption:

 

2.6 A

Ambient temperature:

 

+ 55°C

Semiconductor output current:

 

sum 2.1 A

Relay output:

 

C300, R300

Summary of Contents for PROTECT SELECT

Page 1: ...neral information for electrical connection 4 4 2 Power supply 4 4 3 Start level 4 4 4 Sensor level 4 4 5 Actuator level 5 5 Operating principle and settings 5 1 Connection operating elements 6 5 2 De...

Page 2: ...se If used incorrectly or not for the intended purpose or in the case of tampering danger to persons or damage to machine and system parts from using the safety module cannot be ruled out 1 7 Exclusio...

Page 3: ...t change Sinusoidal max 2 8 Hz max 50 mA s Input resistance 10 k Safe analogue inputs Category PL SIL CL Single channel If a cable break dominates Cat 3 PL d SIL CL 2 Dual channel Cat 4 PL e SIL CL 3...

Page 4: ...d pins Electrical power cables must be routed separately from communication lines 3 2 Disassembly Unlock the bottom of the enclosure by means of a slotted screwdriver push up and hang out slightly til...

Page 5: ...onductor outputs Q2 Q3 with 24 VDC 2 x safe relay outputs QR1 QR2 with common supply QR0 up to 250 VAC or 24 VDC 4 x operational optional message outputs Y0 Y 3 with 24 VDC Relay outputs 250 V 24V GND...

Page 6: ...y outputs Operational outputs signalling output Clock outputs for the supply of safe digital inputs for short circuit recognition 5 3 Start level Alternatively auto start or manual start falling edge...

Page 7: ...processor MSP which is parameter assigned by a three digit hexadecimal number The 1 position describes the sensor the 2 position the additional function and the 3 position the contact properties The e...

Page 8: ...ing locked guard interlocks Power to lock For solenoid locked guard interlocks The interlock type always applies to all connected guard interlocks Analog inputs Dual Sensor 2 channel analysis of AI0 a...

Page 9: ...the list After entry a plain text display of the selected settings appears ENTER moves back to the code list display If you navigate up with the last MSP code the next menu appears MSP 01 1 A 5 MSP 0...

Page 10: ...leshooting Description of possible error cause and rectification measures Restart Trigger of a new start once the error has been eliminated Configuration Enter PIN Entry of the PIN codes so as be able...

Page 11: ...essary Sensors and emergency stop command devices can be reset in any order Sensor level Safe analogue inputs Implemented in the following application programs for both analogue secure inputs are the...

Page 12: ...ital inputs I00 I01 Operating mode selector switch automatic I00 HIGH I01 LOW manual I00 LOW I01 HIGH I02 I03 Enabling switches MSP 6 Default value 0 0 0 I04 I05 1 sensor MSP 2 Default value 0 0 0 I06...

Page 13: ...ayed Signalling output Y3 error message status indication Manual mode Flashing with 2Hz Warning Flashing with 1Hz Error messages Lights up Safe semi conductor outputs Q0 Q0N Stop 0 or Stop 1 All semic...

Page 14: ...lay outputs QR1 QR2 Stop 0 or Stop 1 All relay outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Application...

Page 15: ...4 sensor MSP 5 Default value 0 0 0 I10 I11 5 sensor MSP 6 Default value 0 0 0 I12 I13 Feedback circuit I14 I15 START RESET or latch interlock for I16 I17 I16 I17 Emergency stop command device MSP 1 De...

Page 16: ...00 Monitoring time for MSP 5 T11 10 00 Monitoring time for MSP 6 T12 10 00 Stable time for MSP 1 E Stop T13 0 10 Stable time for MSP 2 T14 0 10 Stable time for MSP 3 T15 0 10 Stable time for MSP 4 T1...

Page 17: ...conductor outputs are linked to a safe timer Timer Off Delay Stop 0 Timer 0 seconds Default value Stop 1 Timer should be actively adjusted to 0 seconds Safe relay outputs QR1 QR2 Stop 0 or Stop 1 All...

Page 18: ...The muting monitoring time continues The muting lamp Y0 remains on The muting outputs remain set e The workpiece releases the light barrier AOPD The muting monitoring time continues The muting lamp Y0...

Page 19: ...art the safety monitoring the high signal is absent at the corresponding input which means the feedback loop of the integrated actuator is not closed Timeout Disturbed safety switch The time lag betwe...