background image

EX-AZ 16

Operating instructions

Safety switch

EN

1

1.  About this document

1.1  Function

This operating instructions manual provides all the information you 

need for the mounting, set-up and commissioning to ensure the safe 

operation and disassembly of the safety switchgear. The operating 

instructions must be available in a legible condition and a complete 

version in the vicinity of the device.

1.2  Target group: authorised qualified personnel

All operations described in this operating instructions manual must 

be carried out by trained specialist personnel, authorised by the plant 

operator only.

Please make sure that you have read and understood these operating 

instructions and that you know all applicable legislations regarding 

occupational safety and accident prevention prior to installation and 

putting the component into operation.

The machine builder must carefully select the harmonised standards 

to be complied with as well as other technical specifications for the 

selection, mounting and integration of the components.

1.3  Explanation of the symbols used

Information, hint, note:

This symbol is used for identifying useful additional information.

Caution:

 Failure to comply with this warning notice could 

lead to failures or malfunctions.

Warning:

 Failure to comply with this warning notice could 

lead to physical injury and/or damage to the machine.

1.4  Appropriate use

The products described in these operating instructions are developed to 

execute safety-related functions as part of an entire plant or machine. It 

is the responsibility of the manufacturer of a machine or plant to ensure 

the correct functionality of the entire machine or plant.

The safety switchgear must be exclusively used in accordance with 

the versions listed below or for the applications authorised by the 

manufacturer. Detailed information regarding the range of applications 

can be found in the chapter "Product description".

1.5  General safety instructions

The user must observe the safety instructions in this operating 

instructions manual, the country-specific installation standards as well 

as all prevailing safety regulations and accident prevention rules.

Further technical information can be found in the Schmersal 

catalogues or in the online catalogue on the Internet:  

www.schmersal.net.

The information contained in this operating instructions manual is 

provided without liability and is subject to technical modifications.

There are no residual risks, provided that the safety instructions as well 

as the instructions regarding mounting, commissioning, operation and 

maintenance are observed.

1.6  Warning about misuse

In case of improper use or manipulation of the safety switch-

gear, personal hazards or damages to machinery or plant 

components cannot be excluded when safety switchgear is 

used. The relevant requirements of the standard ISO 14119 

must be observed.

Content

1  About this document

1.1  Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.2 

Target group: authorised qualified personnel

. . . . . . . . . . . . . . . . . .1

1.3  Explanation of the symbols used . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.4  Appropriate use  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.5  General safety instructions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.6  Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

1.7  Exclusion of liability  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2  Product description

2.1  Ordering code  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.2  Special versions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.3  Destination and use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.4  Technical data  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

2.5 

Safety classification

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

3  Mounting

3.1  General mounting instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

3.2  Dimensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

4  Electrical connection

4.1  General information for electrical connection. . . . . . . . . . . . . . . . . .3

4.2  Contact variants. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5  Set-up and maintenance

5.1  Functional testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5.2  Maintenance  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

6  Disassembly and disposal

6.1  Disassembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

6.2  Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

7  EU Declaration of conformity

x.000 / 10.2016 / v

.A.   -   101

185263-EN / H / 2016-10-24 / 

AE-Nr

. 6668

EN

Operating instructions. . . . . . . . . . . . .pages 1 to 4

Original

Summary of Contents for EX-AZ 16-12ZV(R)K-3D

Page 1: ...ns listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and accident preven...

Page 2: ...nt standards Conditions for safe operation Due to their specific impact energy the components must be fitted with a protection against mechanical stresses The specific ambient temperature range must be observed The user must provide for a protection against the permanent influence of UV rays 2 4 Technical data Equipment category L II 3D Ex protection Ex tc IIIC T90 C Dc X Standards EN 60947 5 1 EN...

Page 3: ... soiling must be removed from the wiring compartment Unused openings must be sealed with EX certified locking screws included in delivery 4 2 Contact variants Contacts are shown with safety guard closed 1 NO 2 NC 3 NC EX AZ 16 12ZV R K 3D EX AZ 16 03ZV R K 3D 13 21 31 14 22 32 11 21 31 12 22 32 5 Set up and maintenance 5 1 Functional testing The safety function of the safety components must be tes...

Page 4: ...y that the hereafter described components both in their basic design and construction conform to the applicable European Directives Name of the component EX AZ 16 L II 3D Ex tc IIIC T90 C Dc X Type See ordering code Description of the component Positive break position switch with separate actuator for safety functions Relevant Directives Machinery Directive Explosion Protection Directive ATEX RoHS...

Reviews: