CSS 8-180
Operating instructions
Safety sensor
EN
Safety inputs X1/X2:
Rated operating voltage U
e
:
24 VDC -15% / +10%
PELV (to IEC 60204-1)
Rated operating current I
e
:
1 A
Accepted test pulse duration on input signal:
≤ 1.0 ms
- With test pulse interval of:
≥ 100 ms
Classification:
ZVEI CB24I
Sink:
C1
Source:
C1
C2
C3
Safety outputs Y1/Y2:
p-type, short-circuit proof
Rated operating current I
e1
:
max. 0,5 A
depending on the ambient temperature
Utilisation category:
DC-12 U
e
/I
e
24 VDC / 0.5 A
DC-13 U
e
/I
e
24 VDC / 0.5 A
Voltage drop:
0.5 V
Leakage current l
r
:
< 0.5 mA
Test pulse duration:
≤ 2.0 ms
Test pulse interval:
2,000 ms
Classification:
ZVEI CB24I
Source:
C0
Sink:
Diagnostic output:
short-circuit proof, p-type
Rated operating voltage U
e2
:
max. 4 V below U
e
Operating current I
e2
:
max. 0.05 A
Utilisation category:
DC-12 U
e
/I
e
24 VDC / 0.05 A
DC-13 U
e
/I
e
24 VDC / 0.05 A
External fuse rating:
fuse:
1.0 A at output current ≤ 200 mA
1.6 A at output current > 200 mA
2.6 Classification
Standards:
ISO 13849-1, IEC 61508
PL:
e
Control Category:
4
PFH:
2.5 x 10
-9
/ h
SIL:
suitable for SIL 3 applications
Mission time:
20 years
3. Mounting
3.1 General mounting instructions
During fitting of the actuator and the sensor, the requirements
of ISO 14119, especially paragraph 7 must be observed.
The component can be mounted in any position. The only condition
is that, the active surface of the safety sensor and the actuator are
opposite. The sensor enclosure must not be used as an end stop. The
safety sensor must only be used within the assured switching distances
≤ s
ao
and ≥ s
ar
.
The safety sensor and the corresponding actuator can be fixed
using the supplied M18 nuts (A/F 24). The max. tightening torque of
the supplied screws is 500 Ncm. Alternatively, the H18 fixing clamp
(accessory) can be used for the fixation of the safety sensor.
A concealed mounting is possible, however this reduces the switching
distance. The reduction will be lower, when the safety sensor protrudes
a few mm.
The CST 180-1 actuator has two fixing holes displaced by 90°. The
max. tightening torque of the supplied screws is 100 Ncm.
The CST-180-2 actuator is screwed into a prepared tapped hole M 18.
Use the slot to the front.
The actuator and/or clamp must be permanently fitted to the
guard system and protected against displacement by suitable
measures (tamperproof screws, gluing, drilling of the screw
heads, pinning).
To avoid any interference inherent to this kind of system and any
reduction of the switching distances, please observe the following
guidelines:
• The presence of metal chips in the vicinity of the sensor is liable to
modify the switching distance
• Keep away from metal chips
• Minimum distance between two sensors: 100 mm
When used at ambient temperatures < -10 °C, the connecting
cables must be hardwired.