schmersal CSS 34F0 Operating Instructions Manual Download Page 5

5

CSS 34F0

CSS 34F1

Operating instructions

Safety sensor

EN

Maximum misalignment from side

Y

X

Actuation from side

The long side allows for a maximum height misalignment (x) of sensor 

and actuator of 36 mm (e.g. mounting tolerance or due to guard door 

sagging). Increased misalignment, max. 53 mm, possible when the 

CST 34-S-2 actuator is used. The axial misalignment (y) is max. 

± 10 mm.

Maximum misalignment from front

Z

Actuation from front

The front face allows for an axial misalignment 

(Z) of max. ± 8 mm.

3.5  Adjustment

The distance between the sensor and the actuator must be set to < s

ao

If variations in the clearance between the sensor and the actuator must 

be detected (e.g. sagging of a safety guard), this distance must be 

reduced by 4 mm. The yellow LEDs and the diagnostic output indicate 

the different ranges.

Recommended Adjustment

Align the safety sensor and actuator at a distance of 0.5 x s

ao

.

The correct functionality of both safety channels must be checked by 

means of the connected safety-monitoring module.

4. Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

The power supply for the safety sensors must provide protection 

against permanent over-voltage. Under fault conditions, the voltage 

must not exceed 60 V. The use of PELV supply units is recommended.

The self-monitoring safety sensors of the CSS 34F0 or CSS 34F1 

series can replace the safety-monitoring module. Therefore, they can 

only be used as first sensor of a series-wired sensor chain (refer to 

operating instructions CSS 34F0 / CSS 34F1).

If a safety chain including multiple sensors is set up, only the first 

device of this chain may be a CSS 34F. type sensor. All other devices of 

the chain must be of the default CSS 34 type. The CSS 34F. performs 

the check of the connected contactors or relays and the optional button 

for the entire chain. 

Requirements for the connected safety-monitoring module

•  Dual-channel safety input, suitable for p-type safety sensors with NO

function.

•  Digital inputs to EN 61131-2, Table "Standard operating ranges for

digital inputs (current sinking)"

The safety sensors cyclically switch off the output to test them. The

switch-off times of max. 500 μs must be tolerated by the switching

device. An extension with short-circuit recognition for the evaluation is

not required. Note on the total length of a safety sensor chain, refer to

paragraph "Series-wiring". The maximum load current of 250 mA per

safety channel must be observed. Contactors with higher load currents

must be controlled by intermediate control relays.

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in the 

online catalogue on the Internet: www.schmersal.net.

If the safety sensor is connected to electronic safety-

monitoring modules, we recommend that you set a 

discrepancy time of 100 ms.  The safety inputs of the safety-

monitoring module must be able blanking a test impulse of 

approx. 1 ms. The safety-monitoring module does not need to 

have a cross-wire short monitoring function, if necessary, the 

cross-wire short monitoring function must be disabled.

4.2  Series-wiring

Series-wiring can be set up. The number of devices is limited for 

safety reasons. Series-wiring of up to 31 CSS 34F0 or CSS 34F1-…-SD 

devices with serial diagnostics is possible. A 200 m long sensor chain 

can be set up. Please note that voltage losses could occur (due to 

cable length, cable section, voltage drop/sensor)! For longer cable 

lengths, the section of the connecting cables must be taken as large as 

possible.

Wiring examples for series-wiring, refer to appendix

Protection is not required when pilot wires are laid. The cables however 

must be separated from the supply and energy cables. The max. fuse 

rate for a sensor chain depends on the section of the connecting cable 

of the sensor.

Wiring capacitance for serial diagnostics

The connecting cable of the safety sensor must have a maximum 

length of 200 m; its wiring capacitance must not exceed 50 nF. 

Depending on the strand structure, normal unshielded 200 m long 

control cables LIYY 0.25 mm² to 1.5 mm² have a wiring capacitance of 

approx. 20 … 48 nF.

When wiring SD devices, please observe the voltage drop on 

the cables and the current carrying capacity of the individual 

components.

Accessories for the series-wiring

For convenient wiring and series-wiring of SD components, 

the SD junction boxes PFB-SD-4M12-SD (variant for the 

field) and PDM-SD-4CC-SD (variant for control cabinet on 

carrier rail) are available along with additional comprehensive 

accessories. Detailed information is available on the Internet, 

www.schmersal.net.

Summary of Contents for CSS 34F0

Page 1: ...formation regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructio...

Page 2: ...ditionally executes functions of a safety monitoring module At both safety outputs two auxiliary contactors1 or relays1 can be connected whose safety related function is checked by the sensor by means...

Page 3: ...3 1 General mounting instructions Please observe the relevant requirements of the standards ISO 12100 ISO 14119 and ISO 14120 The component can be mounted in any position The active surface of the sa...

Page 4: ...ST 34 S 1 CSS 34 S CST 34 V 1 CSS 34 V CST 34 S 3 CSS 34 S CSS 34 V CST 34 S 3 CST 34 S 2 CSS 34 S CSS 34 V CST 34 S 2 CST 180 1 2 CSS 34 S CSS 34 V CST 180 1 2 3 4 Switch distance Actuators and switc...

Page 5: ...es of max 500 s must be tolerated by the switching device An extension with short circuit recognition for the evaluation is not required Note on the total length of a safety sensor chain refer to para...

Page 6: ...The diagnostic output can also be used to detect clearance variations between the sensor and the actuator in the same way as the yellow LED An active fault causes the diagnostic output to be disabled...

Page 7: ...fault Error warning A fault has occurred which causes the safety outputs to be disabled after 30 minutes The safety outputs initially remain enabled This enables the shutdown of the process in a cont...

Page 8: ...1 3 Only version F1 reset button actuation No change compared to 2 The yellow LED is on both connected relays are enabled 1 If no button is used the feedback circuit must be opened by loosening the c...

Page 9: ...enabled by the feedback circuit which is built by the NC contacts of K1 K2 As no further button is used the auxiliary contactors1 or relays1 are immediately enabled when the safety guard is closed The...

Page 10: ...eedback circuit reset button Load Field Control cabinet n participants Wiring example 3 Wiring example for a series wiring of the CSS 34 and CSS 34F1 safety sensors with serial diagnostic outputs The...

Page 11: ...y 8 2 Wiring of the safety sensor with cable or integrated connector Function safety switchgear Pin configuration of the connector 5 8 4 3 2 1 7 6 Colour codes of the Schmersal connectors Poss colour...

Page 12: ...certificate 01 205 5194 02 19 Person authorised for the compilation of the technical documentation Oliver Wacker M ddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal 13 November 2019 Autho...

Reviews: