Operating instructions

Safety sensor

BNS 260 AS

EN

1.6  Warning about misuse

In case of improper use or manipulation of the safety 

switchgear, personal hazards or damages to machinery 

or plant components cannot be excluded. The relevant 

requirements of the standard ISO 14119 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories. 

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

BNS 260 

-AS-

No. Option

Description

Connecting cable (2 m)

STG

Connecting cable with M12 connector (straight)

STW

Connecting cable with M12 connector (angled)

L

Door hinge on the left-hand side

R

Door hinge on the right-hand side

Actuator

BPS 260 -1

Included in standard version

BPS 260 -2

Mounting angle 90°

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The safety sensor is used in AS interface systems for monitoring the 

position of movable safety guards in accordance with ISO 14119 and 

IEC 60947-5-3. The combination of the BNS 260 AS safety sensor, 

the BPS 260-1/-2 actuator and the ASM safety monitor ensures the 

safe monitoring of the condition of the corresponding safety guard. To 

actuate the safety sensor, only the coded BPS 260-1/-2 actuators must 

be used.

The safety switchgears are classified according to ISO 14119 

as type 4 switching devices.

The safety function consists in safely switching off the code 

transmission when the safety guard is opened and maintaining the safe 

switched off condition for as long as the safety guard is open.

An AS-Interface Safety at Work component functions on the basis of 

an individual code generator (8 x 4 bit). This safety code is cyclically 

transmitted over the AS-i network and monitored by the safety monitor.

The component status can be evaluated through a PLC with AS-

Interface master. The safety-related functions are enabled by means of 

the AS-i safety monitor.

LED display

The LEDs have the following meaning (to EN 62026-2):

Green LED

AS-Interface supply voltage

Red LED

AS-Interface communication error or slave address = 0

The user must evaluate and design the safety chain in 

accordance with the relevant standards and the required 

safety level.

2.4  Technical data

Standards:

 

EN 62026-2, IEC 60947-5-3, 

ISO 13849-1, IEC 61508

Enclosure:

 

glass-fibre reinforced thermoplastic,  

self-extinguishing

Coding level according to ISO 14119: 

 low

assured switching distance s

ao

:

 

5 mm

assured switch-off distance s

ar

:

 

15 mm

Protection class: 

IP67 to IEC 60529

Termination:

 

 cable LSYY (0.23 mm² / AWG 24);  

connector M12 x 1, 4-pole

Ambient temperature:

 

–25 °C … +60 °C

Storage and transport temperature:

 

–25 °C … +70 °C

Maximum switching frequency:

 

 1 Hz

Electrical data AS-Interface: 

AS-I voltage range:

 

18.0 ... 31.6 VDC, through AS-Interface, reverse 

polarity-proof

AS-I power consumption:

 

≤ 0.05 A

AS-I Specification:

 

(V 2.1)

 

 AS-i slave profile: S-0.B.F.E, 

IO code: 0x0, 

ID code: 0xB, 

ID code1: 0xF, 

ID code2: 0xE

AS-interface inputs: 

Contact 1: Data bits D0 / D1 = static 00 or  

dynamic code transmission  

Contact 2: Data bits D2 / D3 = static 00  

or dynamic code transmission

Parameter port:

 

 P0 ... P3: no function, set parameter outputs 

 to "1111" (0xF)

Input module address:

 

preset to address 0,  

can be changed through AS-interface bus master  

or hand-held programming device

Diagnostic indication:

 

 

AS-i LED green:  

AS interface supply voltage 

AS-i LED red:  

AS interface communication error 

 

or slave address = 0

For use in NFPA 79 Applications only. 

Only for use in Pollution Degree 2 Environment. 

Adapters providing field wiring means are available from  

the manufacturer. Refer to manufacturers information.

2.5  Classification

Standards:

 

ISO 13849-1, IEC 61508

PL:

 e

Control Category:

  

4

PFH:

 

 6.21 x 10

-9

 / h for ≤ 500.000 operations / year

SIL:

 

suitable for SIL 3 applications

Mission time: 

20 years