background image

4

Operating instructions

Control panel with emergency stop

BDF200-SD

BDF200-FB

EN

3.4  Fixing

Remove the cover of the enclosure a and b (screws: Torx 10)

When opening the enclosure cover, please avoid damage to 

the connecting cables

Caution!

 

Do not touch electrostatically loaded elements  

Do not touch the printed circuit board

Use 2 x M5 cylindral screws ISO 4762 (DIN 912) for the assembly

After fitting, the cover screws must be tightened with a tightening torque 

of 0.7 … 0.8 Nm.

When closing the enclosure cover, please observe that the 

individual cables are not caught between the command 

device and the contact element

a

b

When closing the enclosure cover, ensure that the 

emergency stop module is flush with the bottom section and 

that the cover screws are screwed in as far as they will go

The emergency stop safety function must be checked by 

an appointed safety technician / safety representative once 

successfully installed

3.5  Inscription plates

The marking on the inscription plates (included in delivery) is carried out 

by colour change by laser The effects of heat may change the colour of 

the surface

It must be ensured that the top is inscribed

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by  

authorised personnel in a de-energised condition

The safety outputs can be integrated into the safety circuit of the control 

system To meet the demands of ISO 13849-1 for PL e / category 4,  

the safety outputs of the control panel and control panel chain must be 

connected to a monitor of the same category

Protection is not required when pilot wires are laid The cables however 

must be separated from the supply and energy cables The max fuse 

rating of a device chain for protection of the cable depends on the  

cross section of the cables used

Requirements for the connected safety-monitoring module

•  Dual-channel safety input, suitable for p-type devices  

with normally-open function

Information for the selection of suitable safety-monitoring 

modules can be found in the Schmersal catalogues or in the 

online catalogue on the Internet: wwwschmersalnet

The control panel tests its safety outputs through cyclic deactivation 

The safety-monitoring module therefore does not need to be equipped 

with a cross-wire short detection The switch-off times must be tolerated 

by the safety-monitoring module The deactivation time of the control 

panel is also extended depending on the cable length and the capacity 

of the cable used. Typically, a switch-off time of 250 μs is reached with 

a 30-m connecting cable

Configuration of the safety-monitoring module

If the control panel is connected to electronic safety-

monitoring modules, we recommend a discrepancy time of 

100 ms The safety inputs of the safety-monitoring module 

must be able blanking a test impulse of approx 1 ms  

The safety-monitoring module does not need to have a  

cross-wire short monitoring function, if necessary, the  

cross-wire short monitoring function must be disabled

4.2  Serial diagnostic SD interface

Cable design in case of serial diagnostics

When wiring SD devices, please observe the voltage drop 

on the cables and the current carrying capacity of the 

individual components

The wiring capacitance of the connecting cable of the safety sensor 

must not exceed 50 nF

Depending on the strand structure, normal unshielded 200 m long 

control cables LIYY 025 mm² to 15 mm² have a wiring capacitance of 

approx 20 - 50 nF

Accessories SD interface

For ease of wiring and series-wiring of SD devices 

considerable accessories are available 

Detailed information is available on the Internet,  

wwwschmersalnet 

Summary of Contents for BDF200-FB

Page 1: ...version in the vicinity of the device 1 2 Target group authorised qualified personnel All operations described in this operating instructions manual must be carried out by trained specialist personne...

Page 2: ...ained selector switch 2 or 3 positions WT 2 3 Maintained spring return rotary selector switch 2 or 3 positions SWS SWT 20 Key operated selector switch 2 positions Pos 4 Command and signalling device L...

Page 3: ...urce has to be an isolated secondary source limited by a Listed fuse rated 4A min 24VAC DC Adapters providing field wiring means are available from the manufacturer Refer to manufacturer s information...

Page 4: ...e rating of a device chain for protection of the cable depends on the cross section of the cables used Requirements for the connected safety monitoring module Dual channel safety input suitable for p...

Page 5: ...n of the command and signalling devices The non safety signals of the command devices are transmitted to the control system via the response byte in the SD FB protocol The Illuminated signals are cont...

Page 6: ...ges are not transferred Table 1 Overview of status signals warnings or error messages of SD variant Communication directions Request byte From PLC to local safety switchgear Response byte From local s...

Page 7: ...K BK OUT SD output 5 GY GY GY X2 Safety input 2 6 PK VT PK Y2 Safety output 2 7 BU RD VT IN SD input 8 RD PK OR Connector plug M12 8 pole A coded 9 2 Pin assignment FB variant Function safety switchge...

Page 8: ...ED illuminated push button pos 4 Bit 6 Bit 7 Error reset PLC input data BDF200 FB BDF200 FB SFB PLC Device module SFB module data_1 Sub module Diagnosis and FB interface 6 byte input Slot PROFINET Eth...

Page 9: ...BDF200 SD BDF200 FB Type See ordering code Description of the component Control panel with emergency stop and integrated SD interface or FB interface Relevant Directives 2006 42 EG 2014 30 EU 2011 65...

Page 10: ...A Schmersal GmbH Co KG M ddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal c...

Reviews: