3
BDF200-SD
BDF200-FB
Operating instructions
Control panel with emergency stop
EN
2.5 Technical data
Standards:
IEC 60947-5-1, IEC 60947-5-5, ISO 13850,
ISO 13849-1, IEC 61508, EN 62061
Material of the enclosure:
glass-fibre reinforced thermoplastic,
self-extinguishing
Mechanical life:
command devices: 1 million operations;
emergency stop: 100,000 operations
Connection:
Connector plug M12, 8-pole, A-coded
Lamp socket:
BA5S, LED: max length 17 mm
LED change:
from front
LED power consumption (operating elements):
16 mA
Operating current G24 indicator lamp red/green:
20 mA
Response time:
≤ 50 ms
Duration of risk:
≤ 100 ms
Device category SD variant:
Hex: 41
Ambient conditions:
Ambient temperature:
−25 °C … +65 °C
Storage and transport temperature:
−25 °C … +85 °C
Climatic resistance:
to EN 60068 part 2 - 30
Protection class:
IP65
Protection class:
III
Resistance to vibration:
10 150 Hz (035 mm / 5 g)
Resistance to shock:
30 g / 11 ms
Insulation values to IEC 60664-1:
-
Rated insulation voltage U
i
:
32 VDC
-
Rated impulse withstand voltage U
imp
:
800 V
-
Rated insulation voltage:
III
-
Overvoltage category:
3
Electrical data:
Rated operating voltage U
e
:
24 VDC −15% / +10%
(PELV to IEC 60204-1)
Rated operating current I
e
:
06 A
Required rated short-circuit current:
100 A
No-load current I
o
:
35 mA
Safety inputs X1/X2:
Rated operating voltage U
e1
:
24 VDC −15% / +10%
(PELV unit)
Power consumption per input:
5 mA
safety outputs Y1/Y2:
p-type, short-circuit proof
Rated operating current I
e1
:
max 025 A
Residual current I
r
:
< 05 mA
Utilisation category:
DC-12 U
e
/I
e
24 VDC / 025 A
DC-13 U
e
/I
e
24 VDC / 025 A
Minimum operating current I
m
:
05 mA
Voltage drop:
U
e
< 1 V
Serial diagnostic:
short-circuit proof
Operating current:
150 mA
Wiring capacitance:
max 50 nF
For use in NFPA79, Industrial Machinery, only
The power-source has to be an isolated secondary source
limited by a Listed fuse rated 4A min 24VAC/DC
Adapters providing field wiring means are available from
the manufacturer Refer to manufacturer’s information
2.6 Safety classification emergency stop
Standards:
ISO 13849-1, IEC 61508, EN 62061
PL:
e
Control Category:
4
PFH:
≤ 2.89 x 10
-10
/ h up to max 5,000 switching cycles/year
SIL:
suitable for SIL 3 applications
Service life:
20 years
3. Mounting
3.1 General mounting instructions
There are two mounting holes for M5 screws in the device for attachment
of the BDF200-SD/FB Any mounting position
The relevant requirements of the standard ISO 12100 must
be observed
3.2 Dimensions
All measurements in mm
5.5
M4
209
50
220
19
13.5
40
39
30
20
8
M1
2
27
3.3 Mounting of the pushbutton and illuminated pushbutton caps
for option -2875
The caps for the pushbuttons and illuminated pushbuttons
are only suitable for a one-time mounting Disassembly of the
caps could cause damages to the component
The caps must be mounted immediately after unpacking the
control panel, in order to avoid soiling of the inner pushbutton
compartment by gross dirt particles / dust
The caps for the pushbuttons and illuminated pushbuttons are mounted
in the following manner:
1 Take the pushbutton or illuminated pushbutton cap as well as the
rubber disk out of the kit
2 Take the control panel out of the protective packaging
3 Place the rubber disk on the pushbutton surface
4 Install the pushbutton or illuminated pushbutton cap onto that
5 Fix the cap
The cap "clicks" when it is engaged
6 Check the smooth actuation of the pushbutton
7 Repeat this procedure for all other pushbuttons
After the pushbutton or illuminated pushbutton cap is
mounted, the proper fitting and the smooth actuation of
the pushbutton must be checked The button must return
autonomously from the actuated to the non-actuated state and
the cap must be at the same height as the component edging