2
Operating instructions
Safety-monitoring module
AZR 31S1
EN
There are no residual risks, provided that the safety instructions as well
as the instructions regarding mounting, commissioning, operation and
maintenance are observed.
1.6 Warning about misuse
In case of improper use or manipulation of the safety switch-
gear, personal hazards or damages to machinery or plant
components cannot be excluded. The relevant requirements
of the standards EN 1088 and EN ISO 13850 must be
observed.
1.7 Exclusion of liability
We shall accept no liability for damages and malfunctions resulting from
defective mounting or failure to comply with this operating instructions
manual. The manufacturer shall accept no liability for damages result-
ing from the use of unauthorised spare parts or accessories.
For safety reasons, invasive work on the device as well as arbitrary re-
pairs, conversions and modifications to the device are strictly forbidden;
the manufacturer shall accept no liability for damages resulting from
such invasive work, arbitrary repairs, conversions and/or modifications
to the device.
The safety-monitoring module must only be used when the enclosure is
closed, i.e. with the front cover fitted.
2. Product description
2.1 Ordering code
This operating instructions manual applies to the following types:
AZR 31S1
➀
➁
No.
Option
Description
➀
230VAC
230 VAC
115VAC
115 VAC
24VAC
24 VAC
24 VDC
24 VDC
➁
Pull-in delay 7 sec.
2 sec.
Pull-in delay 2 sec.
This device is designed as dual-channel fail-safe standstill
monitor for monitoring the sensorless motor standstill (no
adjustment required). The nominal motor voltage may amount
up to 400 VAC ±10%.
Only if the information described in this operating instructions
manual are realised correctly, the safety function and therefore
the compliance with the Machinery Directive is maintained.
2.2 Special versions
For special versions, which are not listed in the order code below 2.1,
these specifications apply accordingly, provided that they correspond to
the standard version.
2.3 Destination and use
The safety-monitoring modules for integration in safety circuits are
designed for fitting in control cabinets. They are used for the safe evalu-
ation of the voltage at the inputs L1, L2 and L3
The safety function is defined as the opening of the enabling contacts
13-14, 23-24 and 33-34 when voltage is detected at the inputs L1, L2
and L3. The safety-relevant current paths with the output contacts
13-14, 23-24 and 33-34 meet the following requirements under
observation of a B
10d
value assessment (also refer to "Requirements
to DIN EN ISO 13849-1"):
– control category 4 – PL e to DIN EN ISO 13849-1
– corresponds to SIL 3 to DIN EN 61508-2
– corresponds to SILCL 3 to DIN EN 62061
(corresponds to control category 4 to DIN EN 954-1)
To determine the Performance Level (PL) of the entire safety function
(e.g. sensor, logic, actuator) to DIN EN ISO 13849-1, an analysis of all
relevant components is required.
2.4 Technical data
General data
Standards:
IEC / EN 60204-1, EN 60947-5-1;
EN ISO 13849-1, IEC / EN 61508
Climate resistance:
EN 60068-2-78
Mounting:
Snaps onto standard DIN rail to EN 60715
Terminal designations:
EN 60947-1
Material of the housings:
glass-fibre reinforced
thermoplastic, ventilated
Material of the contacts:
AgSnO, self-cleaning, positive drive
Weight:
115/230 V-version: typ. 400 g
24 V-version: typ. 380 g
Start conditions:
Automatic
Feedback circuit (Y/N):
yes
Pull-in delay:
typ. 7 sec. after the detection of the standstill
(2 sec. variants: after typ. 2 sec.)
Drop-out delay:
immediately after the detection
of a rotary movement < 15 ms
Mechanical data
Connection type:
Screw connection
Cable section:
min. 0.25 mm² / max. 2.5 mm²
Connecting cable:
rigid or flexible
Tightening torque for the terminals:
0.6 Nm
With removable terminals (Y/N):
Nein
Mechanical life:
10 million operations
Electrical life:
Derating curve available on request
Resistance to shock:
10 g / 11 ms
Resistance to vibrations to EN 60068-2-6:
10 … 55 Hz,
amplitude 0.35 mm
Ambient conditions
Ambient temperature:
–25 °C … +45 °C
Storage and transport temperature:
–40 °C … +85 °C
Protection class:
Enclosure: IP40
Terminals: IP20
Clearance: IP54
Air clearances and creepage distances
to IEC/EN 60664-1:
4 kV/2 (basic insulation)
EMC rating:
to EMC Directive
Electrical data
Contact resistance in new state:
max. 100 mΩ
Power consumption:
max. 3.2 W / 4 VA
Rated operating voltage U
e
:
115 VAC / 230 VAC: –15% / +10%
24 VAC / VDC: –15% / +20%,
residual ripple max. 10%
Frequency range:
50 Hz / 60 Hz (AC-operating voltage)
Fuse rating for the operating
voltage (F1):
230 VAC-version: T 32 mA / 250 V
115 VAC-version: T 64 mA / 250 V
24 VAC / VDC-version: T 315 mA / 250 V