6.  Diagnostic functions

6.1  Diagnostic LED's

The solenoid interlock signals the operational state as well as errors 

through three coloured LED’s installed on the front side of the device.

green

Supply voltage on

red

Fault (s. Table: flash codes of the red diagnostic LED

yellow

Operating condition 

6.2  Solenoid interlock with conventional diagnostic output

The short-circuit proof diagnostic output can be used for central 

visualisation or control functions, e.g. in a PLC.

The diagnostic output is not a safety-related output!

Depending on the chosen variant, the following diagnostic signals 

are transmitted:

1P2P variant:

OUT 

guard door closed

1P2PW variant:

OUT 

 combined diagnostic signal: guard door closed and solenoid 

interlock locked

Error

Errors, which no longer guarantee the function of the AZM 200 solenoid 

interlock (internal error)s cause the safety outputs to be disabled 

within the risk time. Any error that does not immediately affect the safe 

functionality of the solenoid interlock will lead to a delayed shut-down 

(refer to table 2).

After fault rectification (fault at output Y1 or Y2, temperature fault), the 

fault is acknowledged by opening and relocking the relevant guard door. 

The safety outputs enable and allow a restart. An interlocking chain 

must be permanently "locked" to enable the reactivation.

If more than one fault is detected at the safety outputs or a 

cross circuit is detected between Y1 and Y2, the solenoid 

interlock will be electronically locked and a normal fault reset 

will no longer be possible. To reset this type of interlocking, 

the solenoid interlock must be isolated from the power supply 

after elimination of the error causes.

Error warning

A fault has occurred, which causes the safety outputs to be disabled 

after 30 minutes. The safety outputs initially remain enabled. This 

enables the shutdown of the process in a controlled manner. An error 

warning is deleted in the slave when the error cause is eliminated.

Behaviour of the diagnostic outputs of the W variant

(Example: power to unlock version)

Input signal magnet control

IN

Normal sequence, door was locked

OUT

Door could not be locked or fault

OUT

Key

Safety guard open

Safety guard closed

Unlock safety guard

Safety guard locked

Locking time:  150 ... 250 ms, 

typically 200 ms

Safety guard not locked or fault

Evaluation of the diagnostic outputs of the W variant

SPS

AZM 200

I N

O U T

E 1 . 0

A 1 . 0

A 1 . 0

E 1 . 0

A 1 . 0

E 1 . 0

M 1 . 0

M 1 . 0

M 2 . 0

M 2 . 0

&

&

A 1 . 0

E 1 . 0

&

A 1 . 0

E 1 . 0

&

Door can be locked

Door can be locked

Power to unlock: IN = 0 = locking

Door is locked

Door is locked

Power to lock: IN = 1 = locking

 

Table 1: the diagnostic function of the AZM 200 solenoid interlock

Summary of Contents for AZM 200

Page 1: ...e with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations an...

Page 2: ...0 with non contact electronic safety sensors is designed for application in safety circuits and is used for monitoring the position of movable safety guards The safety function consists of safely switching off the safety outputs when the safety guard is unlocked or opened and maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open For applications ...

Page 3: ... 10 9 h PFD 2 2 x 10 4 SIL suitable for SIL 2 applications Service life 20 years The safety consideration of the guard locking function only applies for standard devices with monitored solenoid interlock AZM 200 1P2P W see Ordering code The actuation of the interlock must be compared with the external OSSD enabler If a shut down now occurs due to an unintentional unlocking this is detected by an e...

Page 4: ...or is connected to electronic safety monitoring modules we recommend that you set a discrepancy time of 100 ms The safety inputs of the safety monitoring module must be able to blank a test impulse of approx 1 ms The safety monitoring module does not need to have a cross wire short monitoring function if necessary the cross wire short monitoring function must be disabled Information for the select...

Page 5: ...or The safety outputs enable and allow a restart An interlocking chain must be permanently locked to enable the reactivation If more than one fault is detected at the safety outputs or a cross circuit is detected between Y1 and Y2 the solenoid interlock will be electronically locked and a normal fault reset will no longer be possible To reset this type of interlocking the solenoid interlock must b...

Page 6: ...id interlocks can be wired in series For the evaluation of the serial diagnostics line either the PROFIBUS Gateway SD I DP V0 2 or the Universal Gateway SD I U are used This serial diagnostic interface is integrated as a slave in an existing field bus system In this way the diagnostic signals can be evaluated by means of a PLC The response data and the diagnostic data are automatically and permane...

Page 7: ...it 1 7 Set up and maintenance 7 1 Functional testing The safety function of the safety components must be tested The following conditions must be previously checked and met 1 Fitting of the solenoid interlock and the actuator 2 Check the integrity of the cable entry and connections 3 Check the switch enclosure for damage 7 2 Maintenance We recommend a regular visual inspection and functional test ...

Page 8: ...ge must be removed from all components up to the last component The voltage is supplied at both safety inputs of the terminal safety component of the chain considered from the safety monitoring module The safety outputs of the first safety component are wired to the safety monitoring module X1 Y1 X2 Y2 1 2 3 5 6 8 X1 X2 24V GND Y1 Y2 1 2 3 5 6 8 X1 4 Y1 4 Y1 X2 7 Y2 7 Y2 OUT 24V GND OUT SPS PLC IN...

Page 9: ... IN Solenoid control SD input 8 4 RD OR without function 9 6 Connector plug ST1 M23 8 1 pole Connector plug ST2 M12 8 pole 1 2 9 3 4 5 6 7 8 5 8 4 3 2 1 7 6 Connecting cables with coupling female IP67 M23 8 1 pole 8 x 0 75 mm Connecting cables with coupling female IP67 IP69 M12 8 pole 8 x 0 23 mm to DIN 47100 Cable length Part number Cable length Part number 5 0 m 10 0 m 101209959 101209958 2 5 m ...

Page 10: ...onform to the applicable European Directives Name of the component AZM 200 Type See ordering code Description of the component Interlocking device with electromagnetic inter lock for safety functions Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 ...

Reviews: