3

AES 1337

Operating instructions

Safety-monitoring module

EN

Fuse rating of the safety contacts

external (I

k

 = 1000 A)  

to EN 60947-5-1  

Safety fuse 8 A quick blow, 6 A slow blow

Fuse rating of the signalling output: 

Y1: 500 mA  

(internal electronic trip)

Utilisation category to IEC/EN 60947-5-1:

 

AC-15: 230 V / 6 A 

DC-13: 24 V / 6 A

Dimensions (H x W x D): 

100 x 22.5 x 121 mm

The data specified in this manual are applicable when the component is 

operated with rated operating voltage U

e

 ±0%.

2.5  Safety classification

Standards:

 

EN ISO 13849-1, IEC 61508, EN 60947-5-1

PL:

 

up to e

Control category:

 

up to 4

DC: 

99% (high)

CCF: 

> 65 points

PFH value:

 

≤ 2.00 × 10

-8

/h

SIL:

 

up to 3

Service life:

 

20 years

The PFH value of 2.00 × 10

-8

/h applies to the combinations of contact 

load (current through enabling contacts) and number of switching 

cycles (n

op/y

) mentioned in the table below. At 365 operating days per 

year and a 24-hours operation, this results in the below-mentioned 

switching cycle times (t

cycle

) for the relay contacts.

Diverging applications upon request.

Contact load

n

op/y

t

cycle

20 %

525,600

1.0 min

40 %

210,240

2.5 min

60 %

75,087

7.0 min

80 %

30,918

17.0 min

100 %

12,223 

43.0 min

3.  Mounting

3.1  General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.

Snap the bottom of the enclosure slightly tilted forwards in the DIN rail 

and push up until it latches in position.

3.2  Dimensions

All measurements in mm.

Device dimensions (H/W/D): 100 x 22.5 x 121 mm

4.  Electrical connection

4.1  General information for electrical connection

As far as the electrical safety is concerned, the protection 

against unintentional contact of the connected and therefore 

electrically interconnected apparatus and the insulation of the 

feed cables must be designed for the highest voltage, which 

can occur in the device.

The electrical connection may only be carried out by 

authorised personnel in a de-energised condition.

Wiring examples: see appendix

5.  Operating principle and settings

5.1  LED functions

•  K1: Status channel 1

•  K2: Status channel 2

•   U

i

: Status internal operating voltage (LED is on, when the operating 

voltage on the terminals A1-A2 is ON and the fuse has not been 

triggered).

5.2  Description of the terminals

Voltages:

A1
A2

+24 VDC/24 VAC

 

0 VDC/0 VAC

Inputs:

S13 - S14
S21 - S22

Input channel 1
Input channel 2

Outputs:

13 - 14
23 - 24
33 - 34
Y1

First safety enabling circuit
Second safety enabling circuit
Third safety enabling circuit
Signalling output

Start:

X1 - X2

X1 - X3

Feedback circuit and external reset 
(monitored)
Automatic start

K1
U

i

K2

AES 

1337

13 23 33 Y1
A1 X1 X2 X3

14 24 34 S13

A2 S21 S22 S14

Fig. 1

5.3  Notes

Signalling outputs must not be used in safety circuits.

Due to the operating principle of the electronic fuse, the customer 

must check that no hazard is caused by an unexpected restart in 

circuits without reset button (automatic reset).

Summary of Contents for AES 1337

Page 1: ...nce with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description To avoid EMC disturbances the physical ambient and operational conditions at the place where the product is installed must meet the provisions laid down in the paragraph Electromagnetic Compatibility EMC o...

Page 2: ...a PFH value assessment also refer to chapter 2 5 Safety classification Control category 4 PL e to DIN EN ISO 13849 1 corresponds to SIL 3 to DIN EN 61508 2 SILCL 3 to DIN EN 62061 To determine the Performance Level PL of the entire safety function e g sensor logic actuator to DIN EN ISO 13849 1 an analysis of all relevant components is required 2 4 Technical data General data Standards IEC EN 6020...

Page 3: ...IN rail and push up until it latches in position 3 2 Dimensions All measurements in mm Device dimensions H W D 100 x 22 5 x 121 mm 4 Electrical connection 4 1 General information for electrical connection As far as the electrical safety is concerned the protection against unintentional contact of the connected and therefore electrically interconnected apparatus and the insulation of the feed cable...

Page 4: ...lth however at least 1x year Damaged or defective components must be replaced 7 Disassembly and disposal 7 1 Disassembly The safety monitoring module must be disassembled in a de energised condition only Push up the bottom of the enclosure and hang out slightly tilted forwards 7 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with the national pre...

Page 5: ...ossible Dual channel control of magnetic safety switches to EN 60947 5 3 Fig 7 Wire breakage and earth leakage in the control circuits are detected Cross wire shorts between the monitoring circuits are detected Category 4 PL e to DIN EN ISO 13849 1 possible S22 S21 S14 S13 S22 S21 S14 S13 S22 S14 S21 S13 Fig 5 Fig 6 Fig 7 The connection of magnetic safety switches to the AES 1337 safety monitoring...

Page 6: ...Zertifizierungsstelle Elektrotechnik Gustav Heinemann Ufer 130 50968 Köln ID n 0340 EC prototype test certificate ET 16102 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal November 8 2017 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH ...

Reviews: