schmersal AES 1175 Operating Instructions Manual Download Page 2

2

Operating instructions

Safety-monitoring module

AES 1175

AES 1176

EN

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of 

the safety-monitoring module, personal hazards or damages 

to machinery or plant components cannot be excluded. The 

relevant requirements of the standard ISO 14119 must be 

observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages 

resulting from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary 

repairs, conversions and modifications to the device are strictly 

forbidden; the manufacturer shall accept no liability for damages 

resulting from such invasive work, arbitrary repairs, conversions and/or 

modifications to the device.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

AES 117 

No.

Option

Description

5

without start-up test

6

with start-up test

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and therefore 

the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Purpose

The safety-monitoring modules for integration in safety circuits are 

designed for fitting in control cabinets. They are used for the safe 

evaluation of the signals of positive break position switches for safety 

functions or magnetic safety sensors on sliding, hinged and removable 

safety guards as well as emergency stop control devices.

Additionally, two external relays, which can be used for increase in 

capacity or number of contacts, are monitored through feedback 

circuits.

Design

The safety-monitoring module has a dual-channel structure. It includes 

two safety relays with monitored positive action contacts. The NO 

contacts of the relays, which are wired in series, build the enabling 

contacts.

The entire concept of the control system, in which the safety 

component is integrated, must be validated to the relevant 

standards.

2.4  Technical data

Standards:

 

IEC 60204-1, IEC 60947-5-1, IEC 60947-5-3, 

ISO 13849-1, IEC 61508, 

BG-GS-ET-14, BG-GS-ET-20

Start conditions:

 Automatic

Feedback circuit available:

 yes

Start-up test:

 

AES 1175: no,  

AES 1176: yes

Pull-in delay for automatic start:

 

adjustable 0.1 / 1.0 second

Drop-out delay in case of "emergency stop":

 

< 50 ms

Rated operating voltage U

e

:

 

24 VDC ± 15%

Rated operating current I

e

:

 

0.2 A

Rated insulation voltage U

i

:

 

250 V

Rated impulse withstand voltage U

imp

:

 

4.8 kV

Thermal test current I

the

:

 

6 A

Internal electronic fuse: 

 no

Power consumption:

 

< 5 W

Monitored inputs: 

Cross-wire short detection:

 yes

Wire breakage detection:

 yes

Earth connection detection:

 yes

Number of NC contacts:

 1

Number of NO contacts:

 1

Outputs: 

Stop category 0:

 1

Stop category 1:

 0

Number of safety contacts:

 1

Number of auxiliary contacts:

 0

Number of signalling outputs:

 0

Switching capacity of the safety contacts 13/14:

 

6 A

Utilisation category to IEC 60947-5-1:

 

AC-15: 230 V / 3 A 

DC-13: 24 V / 2 A

Max. fuse rating:

 

6 A gG D-fuse

Mechanical life:

 

20 million operations

LED display:

 ISD

Ambient conditions: 

Operating temperature:

 

0 °C ... +55 °C

Storage and transport temperature:

 

−25 °C ... +70 °C

Protection class:

 

Enclosure: IP40  

Terminals: IP20  

Clearance: IP54

Degree of pollution:

 2

Mounting:

 

snaps onto standard DIN rail to EN 60715

Connection type:

 

Screw connection

Min. cable section:

 

0.25 mm²

Max. cable section:

 

2.5 mm², solid strand or multi-strand  

lead (including conductor ferrules)

Tightening torque:

 

0.6 Nm

Weight:

 

190 g

Dimensions (H x W x D):

 

100 x 22.5 x 121 mm

2.5  Safety classification

Standards:

 

ISO 13849-1; IEC 61508

PL:

 

up to d

Control category:

 

up to 3

PFH-value:

  

1.0 x 10

-7

 / h; applicable for applications  

with up to max. 50,000 switching  

cycles / year and max. 80 % contact load.  

Diverging applications upon request.

SIL:

 

up to 2

Service life: 

 

20 years

Summary of Contents for AES 1175

Page 1: ...safety monitoring module must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installa...

Page 2: ...ugh feedback circuits Design The safety monitoring module has a dual channel structure It includes two safety relays with monitored positive action contacts The NO contacts of the relays which are wired in series build the enabling contacts The entire concept of the control system in which the safety component is integrated must be validated to the relevant standards 2 4 Technical data Standards I...

Page 3: ...ng path of the safety monitoring module will open The machine is stopped and the LED flashes yellow Inputs Connect the safety switch or the emergency stop switch to the inputs S13 S14 S21 S22 X1 X2 separate inputs for the feedback of the external contactors Extension of enable delay time On safety guards with strong residual vibrations the end position of a non contact position switch is often ove...

Page 4: ...ses incorrect operation only one contact actuated upon opening or voltage drop perform start up test Table error indications Indication orange LED Error Cause 1 impulse switch Defective supply voltage lead defective switch erroneous fitting of the switch switch only partially ac tuated for at least 5 s 2 impulses The external relay is not pulled in or drops out after being activated Defective supp...

Page 5: ... Test Prüf und Zertifizierungsstelle Fachbereich Elektrotechnik Gustav Heinemann Ufer 130 50968 Köln ID n 0340 EU prototype test certificate ET 17048 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal The currently valid declaration of conformity can be downloaded from the internet at www schmersal net Place and date of issue Wuppertal...

Page 6: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Reviews: