Description of Functions
32 / 52
EN-US · 30.30.01.01963 · 00 · 05/19
6.13.2 Leakage monitoring
Vacuum
Time
SP1
rP1
Measuring the leakage:
In control mode ([
ctr
] = [
on
]), the vacuum drop/leakage over a certain period of time is measured (as
vacuum drop per unit time in mbar/s) from the point when the air saving function interrupts suction after
reaching switching point SP1.
The specified value for the max. permitted leakage -L- can be set in the Extended Functions menu with
the parameter [
-L-
]. Setting the value to [
000
] (= off) deactivates monitoring. The maximum leakage
that can be set is 999 mbar/second.
If the leakage L is greater than the set value -L-, the display will alternately show
-L-
and the vacuum
level.
The
-L-
error message is reset after 5 airtight suction cycles (measured leakage value < specified value).
The message is also immediately deleted if you set the permissible leakage to the value
000
.