background image

ENTWURF

E X P L O S I O N P R O O F

InMax - ... - F1

InMax - ... - SF1

InMax - ... - BF1

InMax -  ...  - CTS

InMax -  ...  - VAS

InMax-...-F1

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

InMax-S-F1_en

V07 – 19-Oct-2021

Subject to change!

Compact. Easy installation. Universal. Cost effective. Safe.

Product views and applications

Description

Highlights

Safety damper

Ball valve

Throttle valve

Electrical rotary actuators for use in safe areas

On-off control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension

8 Nm, 15 Nm with safety operation: fast spring return ~ 1 s*

Type 

Torque  

Supply 

Motor running time   

Spring return*   Control mode   Feedback 

Wiring diagram

InMax-   8 - F1

 

  8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° 

On-off 

 – 

SB 

2.4/2.5

InMax- 15 - F1

 

15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° 

On-off 

 – 

SB 

2.4/2.5

InMax-   8 - SF1

 

  8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off  2 × aux. switches SB 

2.4/2.5 + 3.2

InMax- 15 - SF1

 

15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off  2 × aux. switches SB 

2.4/2.5 + 3.2

InMax-   8 - BF1

 

  8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off  2 × aux. sw tripping circuit  SB 2.4/2.5 + 7.4

InMax- 15 - BF1

 

15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90°  ~ 1 s/90° On-off  2 × aux. sw tripping circuit  SB 2.4/2.5 + 7.4

InMax-  ...  - CTS

  Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)

InMax-  ...  - VAS

  Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)

InMax

  ¼ turn actuators  –  

size S

Industrial use

 Universal supply unit from 24…240 VAC/DC

5 different motor running times 3–15–30–60–120 s/90°, adjustable on site

 On-off control with fast spring return function

 Circuit for direct connection of the ...Pro-TT-... safety temperature trigger 

(type ...-BF1)

 2 integrated auxiliary switches, switching at 5° und 85° (type ...-SF1 and ...-BF1)

 100 % overload protected

 Compact design and small dimension (L × W × H = 210 × 95 × 80 mm) 

 Direct coupling to the damper shaft with double square connection 12 × 12 mm

 95° angle of rotation inclusive 5° pretension

 Robust aluminium housing (optional with seawater resistant coating) or in stainless steel

 IP66 protection

 Simple manual override in preparation for comfortable manual override

 Gear made of stainless steel and sinter metal

 Weight only ~ 3,5 kg

 

Integrated heater for ambient temperatures down to −40 °C 

 Integrated safety temperature sensor 

 Integrated equipment for manual adjustment (push button, lamp, switch)

 Preparation for adaptable and adjustable auxiliary switches type ...Switch

The InMax actuators are a revolution for safety, control and shut-off 

dampers and other motorized applications for HVAC systems in chemical, 

pharmaceutical, industrial and offshore/onshore plants.

IP66 protection, small dimensions, only 3,5 kg weight, universal functions 

and technical data, an integrated heater and an optional stainless steel 

housing guarantee safe operation even under difficult environmental 

conditions. High quality brushless motors guarantee long life.

All actuators are programmable and adjustable on site. Special tools or 

equipment are not required. Motor running times are selectable on site. 

The integrated universal power supply is self adaptable to input voltages 

in the range of 24...240 VAC/DC. The actuators are 100% overload 

protected and self locking.

...Max-...-F1

 actuators are equipped with spring return fail safe function. 

Additionally the 

...Max-...-SF1

 and 

...-BF1

 actuators are equipped with 

2 integrated, potential free auxiliary switches each and 

...Max-...-BF1

 

comes with a tripping circuit for connecting the ...Pro-TT-... safety 

temperature trigger. Standard shaft connection is a double square direct 

coupling with 12 × 12 mm. 

Different accessories are available to adapt auxiliary switches, terminal 

boxes or adaptions for ball valves and throttle valves and other armatures. 

* at temperatures below 

20 °C, depending on the load, the spring return period can be up to 20 sec. If fast spring return below 

20 °C is required, please contact our sales support.

  Please note that nominal values are also subject to tolerances.

1 / 4

Summary of Contents for InMax F1 Series

Page 1: ... H 210 95 80 mm Direct coupling to the damper shaft with double square connection 12 12 mm 95 angle of rotation inclusive 5 pretension Robust aluminium housing optional with seawater resistant coating or in stainless steel IP66 protection Simple manual override included preparation for comfortable manual override Gear made of stainless steel and sinter metal Weight only 3 5 kg Integrated heater fo...

Page 2: ...2 quick connection Aux switches SF1 BF1 2 integrated auxiliary switches switching at 5 and 85 angle of rotation potential free Grid fuse protection is recommended Umax Imax AC 250 V 5 A Umin AC DC 5 V After one time operation with U 24 V AC DC or I 100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload...

Page 3: ...tention During commissioning apply a self adjustment drive Regard duty cycle at motor running times Never use spring return actuators without external load Auxiliary switches see Technical data On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return tripping circuit SB 7 4 Tripping circuit for In Pro TT safety temperature trigger Test button Attention...

Page 4: ...quired minimum of 1 minute the function will be blocked for the rest of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time ...