Schindler 3100/3300/6300
J 43402603 / 01
71/269
Copyright © 2017 INVENTIO AG
4
Maintenance Information and Instructions
4.1
Prerequisites
Basic Principle
Safe operation, efficient and hazard-free maintenance, and rapid response in
emergencies can only be guaranteed if the following points are observed and carried out
by the owner of the installation as his own responsibility.
Restricted Access
Only competent persons are permitted to enter the machine room and hoistway. Building
maintenance and/or cleaning work in the machine room or in the hoistway must be
carried out only by competent persons or in the presence of a competent person. Prior to
such work, all safety measures and precautions must be in place.
Safety Precautions
Lighting
Adequate lighting of the machine room, hoistway and access routes must be guaranteed
at all times. The lighting of the control cabinet for MRL has to be installed by the building
site according to the disposition plan.
Temperature and
Ventilation
The owner of the installation must ensure that the temperature in the machine room and
in the hoistway is maintained b 5 °C and + 40 °C. The machine room and the
hoistway must be adequately ventilated. The machine room and the hoistway may not
be used for ventilating spaces which are not associated with the installation.
4.2
Preventive Maintenance
Scope
Preventive maintenance consists of regular inspection of the electrical and mechanical
safety equipment, additional inspection and adjustment work on the entire installation as
well as lubrication and cleaning. Preventive maintenance does generally not cover the
replacement of components.
Plan of Preventive
Maintenance
Preventive maintenance is carried out in accordance with the maintenance plan
specified by the installer. The maintenance visits depend on various factors relating to
the specific installation and to the environment. Any legal requirements must also be
complied with. The standards define the minimum requirements.
CAUTION
Access Regulations
–
Doors giving access to the machine room and hoistway for maintenance must be
kept locked at all times. It must, however, be possible to open the doors from the
inside without a key.
–
A ladder must be available to permit safe access to the hoistway pit.
–
Access routes to the machine room and hoistway must be easy and safe to pass
through at all times. If one or more of the access routes are blocked, the
installation must be taken out of service.