7 Commissioning
Operating Manual Linear ACTUSAFE CMFS(L)
OM-ENGLISH-Failsafe-Linear-16xx-V2.00-2022.03.03
7
Commissioning
It is assumed that the actuator has been installed and electrically connected correctly. (See section 4, page 27)
NOTE:
Remove silica gel from the alarm cover.
7.1
General information
Technical data
Type
Max. actuators torque
[
Nm
]
Revolutions on the base actuator
In failsafe
direction
Counter
failsafe
direction
nominal
[
mm
]
Revolutions
[
U
]
maximal
[
mm
]
Revolutions
[
U
]
CM03FS(L)30_5
8
16
30
6
35
7
CM03FS(L)50_8
16
32
50
10
55
11
CM03FS(L)100_12
16
32
100
20
105
21
CM06FS(L)100_30
24
64
100
25
105
26,25
CM06FS(L)170_25
24
64
170
42,5
108
45
NOTE:
When commissioning and each time after dismounting the actuator, the electrical end positions have to be reset
7.2
Manual operation
The manual operation is only possible if the actuator is delivered with the optional handwheel. This option allows an ad-
justment of the valve in de-energized state.
CAUTION:
The manual mode can be activated only when the drive is in the failsafe position.
CAUTION:
By activating the manual drive the failsafe function is disabled.
NOTE:
By activating the manual drive the electrical function of the drive is disabled. In normal operation, the hand wheel
(9) has no effect, it rotates idly by.
12