Application Notes
P746/EN AP/G31
MiCOM P746
(AP) 6-
33
7.3.5
CTs on both sides of bus coupler, CB closes before status acquisition.
wrong isolator or CB Status position
2 CT coupler and CB Closes on to external fault with
CT CLOSED
but auxiliary
contact OPEN
CT removed
from Zone 1
I
ExtFault
through CB
P0843ENa
FIGURE 18: CT’S ON BOTH SIDES OF BUS COUPLER,
CB CLOSES BEFORE STATUS ACQUISITION
As the CB has closed but the status has not yet been refreshed the topology still believes the
CB to be open.
AP
Treating this as an open bus coupler the topology algorithm will have extended the two
zones with the areas located between the CTs and the circuit breaker. These then fully
replicate the scheme up to the open bus coupler CB on both sides.
If the circuit breaker was open no load current would flow through the circuit breaker. The
differential current in the two main zones would equal zero, as the current flowing into the
zones would still equal the current flowing out.
However, if the circuit breaker is actually closed, the external fault current will flow through
the circuit breaker. The differential current in the two main zones will be equal in magnitude
but opposite in sign. (
i
fault
)
When the check zone element is calculated, the differential currents seen in the two main
zones, which result from the discrepancy in the plant status and which are taken into account
for the check zone calculation, can be seen to be cancelled out.
Zone 1
I
diff
=
I
1
+ I
2
=
i
diff
Z1 = -i
fault
> (I
D
>2 and k2 x
I
Bias
)
Zone 2
I
diff
=
I
5
+ I
6
=
i
diff
Z2 = +i
fault
> (I
D
>2 and k2 x
I
Bias
)
Check zone
I
diff
=
I
1
+ I
2
+ I
5
+ I
6
=
(-i
fault
) + (+i
fault
) = 0
Hence, the system retains its stability even when there are discrepancies in plant status.
Summary of Contents for MiCOM P746
Page 4: ......
Page 5: ...Pxxx EN SS G11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxx EN SS G11 Page 2 8 Safety Section BLANK PAGE...
Page 16: ...P746 EN IT G31 Introduction MiCOM P746...
Page 18: ...P746 EN IT G31 Introduction IT 1 2 MiCOM P746 IT BLANK PAGE...
Page 26: ...P746 EN TD G31 Technical Data MiCOM P746...
Page 38: ...P746 EN GS G31 Getting Started MiCOM P746...
Page 78: ...P746 EN ST G31 Getting Started MiCOM P746...
Page 80: ...P746 EN ST G31 Settings ST 4 2 MiCOM P746 ST BLANK PAGE...
Page 112: ...P746 EN ST G31 Settings ST 4 34 MiCOM P746 ST BLANK PAGE...
Page 114: ...P746 EN OP G31 Operation MiCOM P746...
Page 136: ...P746 EN OP G31 Operation OP 5 22 MiCOM P746 OP BLANK PAGE...
Page 138: ...P746 EN AP G31 Application Notes MiCOM P746...
Page 142: ...P746 EN AP G31 Application Notes AP 6 4 MiCOM P746 AP BLANK PAGE...
Page 194: ...P746 EN AP G31 Application Notes AP 6 56 MiCOM P746 AP BLANK PAGE...
Page 196: ...P746 EN PL G31 Programmable Logic MiCOM P746...
Page 238: ...P746 EN MR A11 Measurements and Recording MiCOM P746...
Page 240: ...P746 EN MR A11 Measurements and Recording MR 8 2 MiCOM P746 MR BLANK PAGE...
Page 258: ...P746 EN FD G31 Firmware Design MiCOM P746...
Page 280: ......
Page 348: ...P746 EN MT A11 Maintenance MiCOM P746...
Page 350: ...P746 EN MT A11 Maintenance MT 11 2 MiCOM P746 MT BLANK PAGE...
Page 364: ...P746 EN MT A11 Maintenance MT 11 16 MiCOM P746 MT BLANK PAGE...
Page 366: ...P746 EN TS G31 Troubleshooting MiCOM P746...
Page 368: ...P746 EN TS G31 Troubleshooting TS 12 2 MiCOM P746 TS BLANK PAGE...
Page 382: ...P746 EN SC G31 SCADA Communications MiCOM P746...
Page 424: ...P746 EN SC G31 SCADA Communications SC 13 42 MiCOM P746 SC BLANK PAGE...
Page 426: ...P746 EN SG F21 Symbols and Glossary MiCOM P746...
Page 438: ......
Page 440: ...P746 EN IN G31 Installation IN 15 2 MiCOM P746 IN BLANK PAGE...
Page 468: ......
Page 470: ...P746 EN HI G31 Remote HMI HI 16 2 MiCOM P746 HI BLANK PAGE...
Page 500: ...P746 EN HI G31 Remote HMI HI 16 32 MiCOM P746 HI BLANK PAGE...
Page 502: ......
Page 504: ...P746 EN CS A11G31 Cyber Security CS 17 2 MiCOM P746 CS BLANK PAGE...
Page 524: ...P746 EN VH G31 Firmware and Service Manual Version History MiCOM P746...
Page 529: ......