9.1.4. Function test with smoke tube
ATTENTION!
Before a function test, you must make sure that the oil mist detector has been correctly
maintained. Only carry out the function test with the engine at a standstill (if the engine is
running, it will automatically stop or go into slow-down mode).
1.
Figure 72: Remove the screw plug
2.
Figure 73: Fit the adapter hose
Unscrew the screw plug on the inspection
cover of the measuring head and put it
aside.
Screw the quick-release coupling with
sealing ring into the inspection cover and
tighten by hand (Smoke Test Box
151780).
3.
Figure 74: Fit the flex hose
4.
Figure 75: Connect the smoke tube and pump
Connect the flex hose from the Smoke
Test Box (151780) to the adapter
Fit the activated smoke tube and hand
pump to the flex hose.