9.1.2. Maintenance by the operator
WARNING!
Risk of explosion
Severe to fatal injuries due to oil mist explosion
➔
Only use Schaller Automation original spare parts.
9.1.3. Cleaning the light path (4,000 h)
ATTENTION!
Premature failure of the oil mist detector
Dirty parts increase the risk of equipment failure
.
➔
Clean parts according to the maintenance schedule.
1.
Figure 63: Remove screws
2.
Figure 64: Remove seal
Loosen captive screws (x4) on the
inspection cover and twist out of the
measuring head.
Put the inspection cover aside and
dispose of the seal.
3.
Figure 65: Cotton stick with liquid
4.
Figure 66: Clean transmitter diode
Dip a cotton stick into the cleaning
agent.
Clean the glass of the transmitter diode.