Schaffner Group
User and Installation Manual
Ecosine
max
42/66
3.14.2 Filter configuration -E0XXJXX
Filter terminals
Line L1/L2/L3
3 busbar terminals at line side
Load L1’/L2’/L3’
3 busbar terminals at load side
TS, TS’
Connecting terminals to thermal switch NC 180°C (UL-
approved) to detect overload in chokes
AS, AS’
Terminal for auxiliary connection, details refer to section
8.3.7.
PE
Protective earth. Threaded stud with washer and nut
Trap disconnect
D1, D2, D3
D1’, D2’, D3’
3 couples of terminals. For optional configurations with TDJ,
wire bridges are installed for immediate operation of the filter.
They allow for the connection of
|
an external circuit breaker
|
an external circuit breaker together with a remote
control module to disconnect the trap circuit at partial
load
Function blocks
Chokes
Power magnetic components incl. temperature switches
Capacitors
Power capacitors incl. discharge resistors
Trap disconnect
jumper
Terminals for installing circuit breaker or capacitor contactor
by customers themselves