background image

Version Nr. 1-8 - 30.06.2022

Doc. No. 99571511201SG

1 / 20

Table of Content SCE-AC5100B120V

1. User manual 

2

 .................................................................................................................................. 

2. Legal regulations 

2

 ......................................................................................................................... 

3. Safety instructions 

3

 ...................................................................................................................... 

4. Settings 

4

 ......................................................................................................................................... 

5. Functional principle 

5

 ..................................................................................................................... 

6. Technical data 

6

 .............................................................................................................................. 

7. Performance graph 

7

 ...................................................................................................................... 

8. Mounting 

8

 ....................................................................................................................................... 

9. Mounting Principle 

9

 ....................................................................................................................... 

10. Cut out dimensions 

10

 .................................................................................................................. 

11. Dimensions (H x W x D) 

11

 .......................................................................................................... 

12. Electrical connection 

12

 ............................................................................................................... 

13. Controller 

13

 .................................................................................................................................. 

14. Wiring diagram 

16

 ......................................................................................................................... 

15. Taking into operation 

17

 .............................................................................................................. 

16. Trouble shooting 

18

 ...................................................................................................................... 

17. Maintenance & Cleaning 

18

 ......................................................................................................... 

18. Transport & Storage 

19

 ................................................................................................................ 

19. Parts supplied / Spare parts / Accessories 

19

 .......................................................................... 

 

Summary of Contents for SCE-AC5100B120V

Page 1: ...unctional principle 5 6 Technical data 6 7 Performance graph 7 8 Mounting 8 9 Mounting Principle 9 10 Cut out dimensions 10 11 Dimensions H x W x D 11 12 Electrical connection 12 13 Controller 13 14 W...

Page 2: ...instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage Indicates...

Page 3: ...ad with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid sa...

Page 4: ...does not come into contact with the ambient air which may well be dirty or polluted Enclosure cooling units can dissipate large quantities of heat from sealed enclosures such as electrical enclosures...

Page 5: ...gerant thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state it t...

Page 6: ...volume ow system unimpeded Ambient air circuit 385 706 cfm Cabinet air circuit 235 324 cfm Mounting Wall mounted Housing Material Mild steel powder coated Dimension H x W x D 45 2 x 15 5 x 10 6 inch...

Page 7: ...Version Nr 1 8 30 06 2022 Doc No 99571511201SG 7 20 7 Performance graph...

Page 8: ...ect the air ow Cooling unit enclosure air suction hole must be installed in the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure en...

Page 9: ...lation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary The bracket helps with the mounting of th...

Page 10: ...Version Nr 1 8 30 06 2022 Doc No 99571511201SG 10 20 10 Cut out dimensions...

Page 11: ...Version Nr 1 8 30 06 2022 Doc No 99571511201SG 11 20 11 Dimensions H x W x D...

Page 12: ...ing to EN60730 1 8 4 A N O 6 4 A N C 2 2 A N O N C 250Vac 100000 cycles UL 873 8A resistive 2FLA 12LRA pilot duty C300 250Vac 30000 cycles These contacts are not suitable for uorescent loads neon ligh...

Page 13: ...ress 2 Alarm relay active 3 Heater relay active 4 Ambient blower relay active Alarm Flashes when alarms are active Heating mode Signals operation of unit in heating mode Cooling mode Signals operation...

Page 14: ...for high temperature alarm threshold default 55 C 131 F 3 Press SET on the desired parameter to display the current value 4 Use or to reach the desired value 5 Pressing SET temporarily saves the new v...

Page 15: ...on ashes Typical alarm codes Error Code Description E01 Probe B1 fault E02 Probe B2 fault E04 High temperature alarm E05 Low temperature alarm Important Notes Whilst programming if no button is presse...

Page 16: ...Version Nr 1 8 30 06 2022 Doc No 99571511201SG 16 20 14 Wiring diagram 1 L1 2 3 N 4 PE 5 Alarm contact NO P1 6 Alarm contact COM P2 7 Alarm contact NC P3 8 Door contact T1 9 Door contact T2...

Page 17: ...he unit system must be protected with a MCB Type D or K Upon connection the internal fan will start working If the temperature inside the enclosure is higher than the set value of the controller both...

Page 18: ...e time Cooling unit undersized Enclosure needs a cooling unit with with higher capacity Compressor and external fan work in alternating mode ON OFF Thermal compressor protector triggered Verify if amb...

Page 19: ...nit To avoid transport damage the unit should be returned in the original packing or in a packing case and must be strapped to a pallet If the unit cannot be returned in the original packing please en...