Document
9911004rev27
Title
Date
2017-02-16
Page
74(81)
SBS MicroSMART Battery Charger Technical Handbook
Capacity
Battery capacity in ampere hours used in this
charging cycle.
Cells
2 V battery cell count used in this charging cycle.
Cable Ri
Battery cable resistance used in this charging
cycle.
Base load
Base load being present in the charging circuit
during charging used in this charging cycle.
Charger model
The power unit description.
Start heat sink temp
Temperature of the heat sink when battery
connected. Measured before start of charging.
End heat sink temp
Temperature of the heat sink when battery
disconnected. Measured after disconnection of
the battery.
Max heat sink temp
Maximum temperature of the heat sink between
Charge start time
and
Charge end time
.
Alarms
Blank if no alarms present during charge cycle.
Text according to alarm description in charger.
Event index start
Index of the
Event log
at start of charging.
Event index end
Index of the
Event log
at end of charging.
A difference in
Event index start
and
Event index
end
indicates that there have been some errors or
other events during the charging cycle. See event
log with
Event index
between
Event index start
and
Event index end
for details.
Charge total index
Total charge cycle count since startup.
This number can be used as a unique identifier of
the charging cycle in case a
Clear statistics
is made
in the charger.
11.2.
Event log
Event index
Event identifier.
If
Clear statistics
is made in the Charger this index
starts over on 1.
Event time
Time stamp when the event occurred in the
charger. Charger local time.
ID
Event identifier, the following variants exists:
1.
Time is set
2.
Charge started (not used)
3.
Charge ended (not used)
4.
Alarm
5.
Alarm